           In NOJA Power’s OSM Recloser        If the race to disconnect load is faster than the frequency falling, a network can regain
        system, the over-frequency feature   control by reaching the point where remaining generation matches the load that is left
        monitors the power frequency and can   connected to the network.
        be configured to either alarm or trip the   At this point, network operators can progressively increase power, and reconnect parts
        recloser if the frequency goes too high.  of the network, avoiding a complete blackout event.
                                               Under-frequency works by monitoring the system frequency to see if it reaches a
        Under-frequency                      threshold below the operating frequency. If this occurs, the relay activates and can either
        Under-frequency occurs when there is a   automatically trip a circuit breaker or alert the network operator.
        generation shortfall. That is, when there is
        too much load for the available generation   Rate of change of frequency
        capacity.                            The last frequency element for consideration is rate of change of frequency, known as
           Under-frequency protection is often   ROCOF.
        used in a “load shedding scheme”, where   This protection deals with a fundamental shortfall of over-frequency and under-
        the distribution network automatically   frequency protection – the non-detection zone.
        disconnects parts of the network when   Both over- and under-frequency protection require the network conditions to become
        there is insufficient generation.    critical before they are detected.
           This allows the network operator to   If the network is normally at 50 Hz, and a generation shortfall occurs, a circuit breaker
        partially reduce service, rather than allowing   without ROCOF would only know about the problem when the frequency reaches a low
        the entire system to experience a blackout.  point. By this time, the frequency may have fallen too far to be saved by load shedding.
           Using OSM Reclosers positioned      Instead, ROCOF looks at the movement of frequency over time. While minor
        around the distribution network, these   movements in frequency are tolerable, a major shift of say 0,5 Hz/s, is more indicative of
        devices can be automatically triggered   serious issues.
        to “shed load” by progressively powering   By monitoring ROCOF, circuit breakers can operate faster, because the protection
        down parts of the network when there is   system can see the problem before the frequency has dropped.
        insufficient generation.               Using our car analogy again, ROCOF is like the eyes of the driver. ROCOF can see the
















































        Figure 1: Multiple NOJA Power OSM reclosers installed in a distribution substation



                                                    energize | June 2022 | 66