Page 21 - EngineerIt May 2021
P. 21

AUTOMATION AND CONTROL



           The M-LB-5000 modules are mounted on a standard DIN    However, if the signal circuit needs to be intentionally
        mounting rail. The devices each consist of a base module and   interrupted — for isolation tests during commissioning or in recurring
        the actual protection module. The system also has an insulating   tests — the protection module can simply be rotated by 180 degrees
        partition to maintain clearance when mounting Ex and non-Ex   and plugged in. In this case, the signal circuit is interrupted by an
        modules on a DIN mounting rail. All modules have a width of only   integrated isolating function. This allows the module to replace
        6.2 mm and allow simple commissioning without special aids.   terminal blocks in the cross connect level with no additional space
        In addition to the protection and base modules, there are three   required. This combination of condition monitoring, more than 100
        function modules. The maintenance module reports when a   modules per function module block, loop separation, and 6.2 mm
        yellow LED lights up on at least one protection module, indicating   width with single-loop integrity, is unique on the market.
        that this module should be replaced. The fault module indicates
        when at least one device has a fault (red LED) and needs to   Terminal block with surge protection
        be replaced immediately. The third unit is a power module that   Pepperl+Fuchs has developed the M-LB-2000 for applications
        powers the protection modules via the power rail. The error   requiring only minimum specifications plus loop connect. It has a
        messages are also sent to the function modules or the control   form factor very similar to the M-LB-5000 and is designed to be
        panel via the power rail.                              attached directly to the DIN mounting rail. The main differences
                                                               are that the module cannot be diagnosed or replaced without
        Protection modules with signal LEDs                    interrupting the signal line. A loop disconnect function is achieved
        The intuitive, easy-to-read traffic light display on the protection   when the module is plugged in via two easily accessible switches
        modules greatly reduces testing effort since the fault can very   on the front.
        easily be assigned to a specific signal circuit. A green LED on   The M-LB-2000, which is also only 6.2 mm wide, not only
        the protection module means that the full protective effect is   saves a lot of space in the switch cabinet, it practically replaces
        present, there is a sufficient functional reserve, and there is no   the terminal block with surge protection. This means that
        need for action. As part of the condition monitoring function,   disconnect terminal blocks are no longer necessary, saving costs.
        the yellow LED signals that the protection module has reached   The certificates range from ATEX, IECEx, Zone 1 and SIL 3.
        90 % of its life cycle. The signal circuit is still protected, but the
        module should be replaced soon, for example during the next   Conclusion
        regular servicing. A red LED indicates that the protection module   The M-LB-5000 surge protection system’s diagnostics use a
        may be permanently damaged and no protective effect can be   special algorithm to detect different load situations and send
        guaranteed. It should be replaced immediately to prevent damage   a signal when the protection module has reached 90 % of
        during the next surge voltage event.                   its life cycle. This significantly increases the efficiency of the
                                                               protective function and keeps maintenance costs to a minimum.
        The benefits of modularity                             The modularity of the device enables the protection module
        During maintenance, the modular assembly of the surge protection   and loop disconnect to be replaced without tools and without
        system offers significant advantages compared with conventional   interrupting operation.
        solutions. Due to the base module on the DIN mounting rail,   The M-LB-2000 with loop disconnect function is designed
        removing the protection module does not cause a signal   for significantly lower requirements in surge protection. With a
        interruption. The signal circuit is closed without interruption via the   width of 6.2 mm, it saves just as much space in the switch cabinet
        base module, at the moment when the connection between the   and can be used as a replacement for the terminal block with
        signal circuit and the protection module is no longer established.   surge protection.                  n
        A protection module can therefore be replaced without affecting
        plant operation. An additional loop check is not necessary.  For more information visit www.pepperl-fuchs.com






                 Contact Merinda Lottering for all your advertising requirements

                        Cell: 071 765 5702  |  Email: merindal@nowmedia.co.za





















                                                    EngineerIT | May 2021 | 19