Page 34 - Energize June 2021
P. 34

TECHNICAL

        Reducing the risk of failure of HV



        instrument transformers





        Information from Megger


        The application of narrowband dielectric frequency response (NB DFR) on HV CVTs to reduce the risk of
        failure of HV instrument transformers in the transmission system.





        A case study: A utility’s SCADA system indicated a loss of
        voltage in one phase. Since 765 kV CVTs provide the voltage
        information to all control, metering, and protection systems at this
        location, failure of the CVT (CVT-1) corresponding to that specific
        phase was immediately suspected. Tests, which were conducted
        on the capacitance and power factor (PF) at line frequency,
        confirmed insulation failure of C1 sections B2 and B3 of CVT-1
        (see Figures 1 and 2).
           For additional insights, 250 V narrowband dielectric frequency
        response (NB DFR) tests, comprising PF measurements between 1
        and 500 Hz, were performed on all four sections of CVT-1 (Figure 3).
           The customer reported this fairly obvious failure as an over-
        pressure event and replaced CVT-1 with CVT-1R. CVT-1R was
        similarly tested. Its acceptable capacitance and PF and NB DFR test
        results serve as helpful, normative references for CVT test results   Figure 3: NB DFR plot of failed CVT 1’s C1 sections B1 to B4 (Note the
        (Figures 4 and 5).                                     PF at 60 Hz in the 250 V NB DFR test results above. When compared
                                                               to the 10 kV PF test results in Figure 1 significant, abnormal voltage
                                                               dependencies become obvious.).






        Figure 1: Megger delta control results of CVT-1’s C1 sections B1 to
        B4 (Note elevated PF results, significant discrepancies in capacitance
        between sections and high, non-zero VDFs, which indicate PF voltage
        dependencies, in sections B2 and B3).                  Figure 4: Acceptable capacitance and PF test results for replacement
                                                               CVT-1R (Note that a ratio test performed at 10 kV and a digital
                                                               multimeter indicated acceptable ratio results).





















                                                               Figure 5: Acceptable NB DFR test results for replacement CVT-1R C1
        Figure 2: CVT simplified scheme.                       sections B1 to B4.



                                                    energize | June 2021 | 32
   29   30   31   32   33   34   35   36   37   38   39