Page 35 - Energize June 2021
P. 35

TECHNICAL



           While replacing CVT-1, the testing specialist noticed a stain   Lessons learned
        on the surface of the adjacent phase CVT (CVT-2, Figure 6).   •  A CVT in good condition should have a very low PF value (at
        CVT-2 was reporting an expected voltage in SCADA but given the   20°C) <0,2% at 1 Hz (Figure 5).
        failure of CVT-1 and convenient access to the testing equipment,   •  The utility performs monthly visual inspections but did not notice
        capacitance and PF tests and NB DFR tests were performed on   the oil leak between C1 sections of CVT-2. Testing averted its
        CVT-2 too (Figures 7 to 10). These tests revealed insulation failure   likely failure.
        in CVT-2.                                              •  NB DFR testing will be incorporated in the utility’s future routine
           A disassembly of CVT-2 confirmed significant damage to its    maintenance of CVTs.
        C1 – B1 section (Figure 11).                           •  The Megger Delta4000 and TDX120 provide both basic (capacitance
           A puncture was found in the C1-B1 section, and oil was   and PF) and advanced (NB DFR) diagnostic insulation testing.
        missing from the top portion of C1-B1 section. Although its   Atypical NB DFR results should be further investigated with a full
        insulation integrity was compromised, its ratio was not affected.   dielectric frequency response (DFR) test using the Megger IDAX300.n
        CVT-2 was also replaced.
                                                               Contact Marie-Claude Rasendra, Megger,
                                                               marie-claude.rasendra@megger.com




















                                                               Figure 9: NB DFR test results 1 to 500 Hz on CVT-2 (Note that all units
                                                               connected in series have been affected and the dielectric response
                                                               presents an atypical response for all four sections. The 1 Hz test result
                                                               of C1 section B1 revealed a different behaviour compared to the other
                                                               sections and a PF tip-up test (Figure 10), was performed to verify its
                                                               voltage dependence.).



        Figure 6: CVT-2 as found during visual inspection (Note that a ratio test
        performed at 10 kV and a digital multimeter indicated acceptable ratio
        results.).





        Figure 7: C1-B1 section capacitance and PF test results for stained
        CVT-2.
                                                               Figure 10: Power factor tip-up test results for C1-B1 section of CVT-2.















        Figure 8:10 kV line frequency PF test results for C1 sections Bi to B4 of
        CVT-2 (Note the elevated PF for Ci-B1 section (0,25%) relative to the
        other three sections (~0,08%)).                        Figure 11: Oil overflow due to puncture on top of C1-B1 section.



                                                    energize | June 2021 | 33
   30   31   32   33   34   35   36   37   38   39   40