Page 39 - Energize June 2021
P. 39

TECHNICAL



        emergency lights will require circuitry to activate the lamp upon   Standby lighting
        supply failure. Non-maintained units will require separate feeds   Stand-by lighting is a non-mandatory part of emergency lighting
        from the maintained units or means of signalling mains failure to   that is provided to enable normal activities to continue substantially
        the luminaire. A CBS system may require fireproof cabling whereas   unchanged. Stand-by lighting is usually used where a standby
        self-contained uses normal cabling. Cabling requirements can   generator provides power to the building, and may involve all of
        be reduced by the use of distributed control. Control units, that   the normal lighting units, or a reduced number of normal lighting
        may incorporate mains fail detectors, are placed in a zone to feed   units. Stand-by lighting is typically seen today in supermarkets and
        power to both maintained and non-maintained emergency lights   shopping malls, where a limited number of lights are kept on during
        from the same feed, from the CBS.                     load shedding.
                                                                 Some emergency lighting standards have introduced the
        Testing and maintenance                               concept of “Emergency Safety Lighting” (ESL) or “Stay Put
        Any of the components in an emergency lighting system can   Lighting” in response to the increasing application of emergency
        fail and regular testing is required to ensure operation of the   lighting to assist the safety of occupants who may stay in a
        luminaire. All emergency lighting systems must be tested monthly.   building during a failure of the grid power supply and ensure
                                                                             4
        The period of simulated failure should be sufficient for the purpose   business continuity.  This situation is particularly relevant to load
        of this test while minimising damage to the system components.   shedding. In buildings where there is adequate natural lighting and
        During this period, all luminaires and signs shall be checked to   no other reason to evacuate, ESL can be applied effectively to
        ensure that they are present, clean and functioning correctly.   allow continuation of activities under load shedding. ESL should
           An endurance test for the full duration of the emergency   help occupants continue normal operations in the event of failure
        lights must be carried out once a year. The emergency lights   of the supply to normal lighting.
        must still be working at the end of this test. The result must be   The ESL may use separate lighting fixtures or may make use
        recorded and, if failures are detected, these must be remedied   of normal lighting fixtures combined with control circuits that limit
        as soon as possible. Any batteries that do not last the required   the number of lights that are switched on during load shedding.
        period should be changed immediately. Life expectancy will vary   Addressable lighting units connected to a lighting control unit or
        depending on the make of the battery; with some makes it is four   building management system can be used effectively to provide ESL,
        years, some five years. When the life expectancy date expires   as the number of lights on in an area can be set by the control unit
        the batteries should be changed. It is a good idea that when a   and varied as necessary.
        battery is changed the date of installation is written on the battery   This is particularly applicable in situations where the building is
        for future reference.                                 equipped with standby generators and UPS systems intended to keep
                                                              essential loads running, but which could not cope with the full lighting
        Automatic test systems                                load of the building.
        Manual testing and record keeping of emergency lighting is time-  Lighting levels under ESL may be lower than the required levels,
        consuming and is often neglected. There are numerous automatic   but should still enable safe use of office or other equipment. In “high
        test systems (ATS) available on the market that can be operated   risk task areas” the illuminance value should not be less than 10% of
        separately or integrated into building management systems. ATS   the average of the normal lighting at the location of the risk. In some
        make it possible to test at short intervals and can keep records of   applications, such as hospital operating theatres, 100% of normal
        such things as duration, battery capacity, etc.       lighting levels may still be required.
           These systems have built-in processors that enable self-  If there is an ESL solution, the emergency action plan should
        diagnosis, reporting and record keeping. This feature drastically   make it clear how long occupants can stay and how the end of the
        reduces maintenance costs because no manual emergency   ESL period will be indicated. The plan should also make clear what
        lighting tests are required. These units are programmed to   happens at the end of the emergency duration and how occupants
        continuously monitor the state of the emergency lighting system   will be directed to safe exits. A maintenance plan also needs to be
        and carry out the required function and duration tests. The fitting   established, even if ELS is self-testing. Standby lighting is not a
        will report, by a flashing code or buzzer, the nature of the fault   substitute for emergency lighting, as the standby power supply could
        which alerts the technician to replace the lamp or the battery.   fail while grid power is absent.      n

        Addressable systems                                   References
        Addressable emergency lighting systems are available that can   1.  Department of Labour: “Occupational health and safety ACT”.
        be incorporated into a lighting control system (LCS) or building   2.  S Marais: “South African Emergency Lighting Guide”, Cosine
        management system. The system can perform all the required   developments, 2011.
        operating tests on lighting units, and produce reports on the   3.  Thomas & Betts: “Emergency lighting guide”, www-public.tnb.com/
        results of the tests. Tests could be carried out automatically   4.  R MacPartland: “Emergency safety lighting - revisions to BS
        at predetermined times, or under manual control. The control   5266”, www.thenbs.com/
        unit can provide information in graphic form on the state of the   5.  SABS: “SANS 10114-2:2020 Interior lighting, Part 2: Emergency
        system, the configuration of the luminaires, the possibility of   lighting”.
        connecting the luminaires to the control unit, the operating state
        and the autonomy period of each lighting unit.        Send your comments to rogerl@nowmedia.co.za



                                                    energize | June 2021 | 37
   34   35   36   37   38   39   40   41   42   43   44