Page 48 - Energize June 2021
P. 48

TECHNICAL



        Passive arc-resistant switchgear
        Passive arc-resistant equipment attempts to contain the AF within
        the body of the switchgear, and typically provides increased
        protection through strengthened enclosures and the venting of
        pressurized hot gases and other arc products. Additional protection
        on LV switchgear can be provided by solid insulation on all exposed
        conductors such as busbars connection points, etc.

        Active arc-resistant switchgear and techniques
        One drawback of passive arc-resistant switchgear is that while it
        provides a significant degree of protection to workers, it may not
        do anything to reduce the intensity or duration of the internal arcing
        fault itself. The equipment may be designed to contain the blast, but
        the internal damage may be significant, requiring either re-work or
        replacement of the switchgear. Active arc-resistant or arc reduction
        (AR) switchgear is equipment designed to reduce incident energy,
        shorten clearing times, or redirect energy away from the arc.
                                                               Figure 2: Operation of current limiting fuse (Eaton)
           AR switchgear systems use devices that limit the energy in
        the arc by limiting the current flowing or the duration of the arc.
        The devices may be incorporated in the body of the switch or   an optimal balance between arc flash reduction and maximizing
        be mounted externally. Placing a device that limits arc energy in   selectivity. This requires that arc flash be considered as part of the
        non-arc-resistant switchgear could meet the requirements for arc   device. When replacing thermal-magnetic breakers with devices
        resistant switchgear.                                  which have an electronic trip unit, or upgrading older trip units with
                                                               modern trip units, it would make  good sense to add the IT setting
        Current limiting devices                               to the operating portfolio.
        The extent of an AF can be reduced by limiting the current flowing in
        the arc circuit by current-limiting fuses or reactors. Current-limiting   Arc flash reduction maintenance system (ARMS)
        fuses act very quickly when the fault current levels are high enough   This is deployed as a part of the internal trip unit of air circuit
        to cause the fuse to respond in its current-limiting region. Current-  breakers. The protection curve in any low voltage air circuit breaker
        limiting fuses operate by creating additional arcs within the fuse   trip unit allows settings of variable time and instantaneous operation
        structure, increasing the voltage across the fuse and decreasing   for selective coordination. ARMS offers a separate protection
        the voltage across the arc. For normal fault currents the fuse takes   setting that, when enabled in the maintenance mode, overrides the
        several cycles to operate. Current is limited by the fuse operating   standard settings and reverts to a predetermined instantaneous
        before the maximum possible peak current is reached (Figure 2).  trip setting. The advantage of this is a significant reduction in total
                                                               clearing time, which in turn reduces the arc flash hazard.
        Reduction of fault clearing times
        The best and most direct way to reduce arc-flash hazards is to   Arc flash protection relays (AFP)
        reduce fault-clearing times, thereby reducing the overall incident   The purpose of these relays is to detect an arc flash and operate
        energy. The energy released in an arc flash is dependent on the   fast trip circuit breakers serving the zone where the AF occurred.
        duration of the arc, and hence the fault clearing time. (Figure 3).  AFP could be separate units or may be incorporated into the switch
           Circuit breakers with adjustable trip settings, which cater for   control relay in more modern systems. Some modern simplified
        shaping of the device tripping curves, allow for performance across   switchgear protection relays incorporate arc flash protection as a
        a broad range of fault current levels. This allows an instantaneous   standard function and do not require separate AFP relays. Detection
        tripping (IT) setting, which can be activated by an external signal,   is on a zone basis, and AFPs generally cater for more than one zone.
        to be used for arc flash reduction. Breaker settings should strike   The AFP is effective in reducing the time to disconnect the arc.



















          (a) Incident energy                                          (b) Damage caused by incident arc energy
        Figure 3: Duration of fault vs incident energy (ABB)



                                                    energize | June 2021 | 46
   43   44   45   46   47   48   49   50   51   52