Page 59 - Energize October 2021
P. 59

TECHNICAL



           In a new cable the voltage and current in the cable under test   none of the results can be related to the IEC method. These methods,
        will be close to 90° out of phase due to the high resistance of the   which are more suitable for on-line monitoring and measurement,
        insulation, and tan δ value will be low. As the insulation ages, the   include the use of HF transformers, piezo devices and acoustics. The
        angle will decrease and tan δ becomes higher and becomes more   HF transformer and coupling capacitor methods are the most reliable
        voltage dependent. Water trees exhibit a capacitance that increases   when it comes to on line measurement. 2
        with voltage, so the tan delta measurements taken at higher voltage
        increase (see Figure 5). This plays an important part in analysing   Background noise
        cable condition. 3                                     A major challenge is that PD energy quantities are usually minute
                                                               compared to the ambient or background noise. If PD current is the
                                                               parameter being measured, a typical PD event involves several tens of
                                                               pico-Coulomb (pC) charge transfer in tens of microseconds, and the PD
                                                               current pulse magnitude can be in the order of one μA. Measurement
                                                               of such a minute current in an environment of typical power system
                                                               load currents and electromagnetic interferences is problematic, and
                                                               extraction of PD signals from the noisy environment is a major frontier
                                                               of research in PD technology. Significant progress, however, has
                                                               been achieved in developing effective techniques of noise mitigation
                                                               in PD diagnosis. In that regard most commercial PD measurement
                                                               technologies have state-of the art PD noise management although
                                                               there is still room for improvement.

                                                               Key parameters for PD analysis
                                                               The following are the main parameters used in PD analysis:
                                                               •  PD count: The number of PD incidents occurring during the test.
        Figure 5: Effect of age and voltage on Tan delta measurements 5  •  PD intensity: The level of the PD discharge for each incident
                                                               •  Partial discharge inception voltage (PDIV): This is the voltage at
        Partial discharge (PD) testing                           which PD events start to occur. It has been shown that PDIV is a
        Partial discharge, or PD, is caused by local electrical stress in the   function of test voltage frequency or the rate of change of voltage
        insulation or on the surface of the insulation in electrical equipment.   (dU/dt), in the region of the zero crossing during polarity reversal.
        It not only indicates insulation defects but it is also responsible   The inception voltage for surface discharges and internal discharges
        for developing them. PD is therefore a good indicator of dielectric   in layered interfaces, like splices and terminations, is particularly
        condition and is present well in advance of insulation failure. PD is the   sensitive to the voltage gradient. 2
        predator of insulation. Once damage has started it cannot be stopped.   •  Partial discharge extinction voltage (PDEV): This is the voltage at
        Partial discharges are often regarded as both symptoms and agencies   which an existing PD event extinguishes. There is no known direct
        of power cable degradation.                              correlation between PDIV and PDEV, but the parameters follow a
           Power cable failures account for most of power distribution system   hysteresis pattern. Empirical observations and practical experience
        failures, and most are caused by partial discharge activity in power   indicate that PDEV levels are typically between 0,8 and 0,9 times
        cable accessories.  Improved reliability of power cable systems entails   PDIV and sometimes as low as 0,7 times. It has been found that PD
                    1
        early detection and mitigation of incipient PD faults. The recommended   activity extinguishes with very slow dU/dt, which makes it difficult to
        method (IEC 60750) of PD testing involves detection and measurement   conduct PD measurements using low frequencies like 0,1 Hz. Only a
        of PD discharge currents. The method is offline and involves the use of   damped oscillating voltage source (DAC) can properly measure PDIV
        a test equipment set-up as shown in Figure 6. Discharge currents are   and PDEV in the same test cycle. 2
        measured in picocoulombs (pC).
           There are other methods of detecting and measuring PD but   Test procedure
                                                               Testing is carried out by increasing the voltage in regular steps at regular
                                                               intervals as shown in Figure 7.
                                                                  Once a PD has been detected, the impact on the insulation
                                                               integrity and life of the cable has to be determined through
                                                               interpretation of the PD signal. Usual parameters used are the number
















        Figure 6: PD measurement according to IEC 60750 4      Figure 7: PD testing procedure (Megger)



                                                   energize | October 2021 | 57
   54   55   56   57   58   59   60   61   62