Page 7 - Energize November 2021
P. 7

COVER STORY



          Strategic maintenance always comes with
        associated start-up costs, and it is advisable to
        implement maintenance strategies for a minimum
        of two to three years to accurately monitor and
        record the savings from start-up to current levels.
        This is when the maintenance strategy delivers
        the results being sought and thereby supports
        the optimisation of networks, which in turn has
        positive results on increasing production and
        minimising downtime.
          It is advisable to use the services of specialist
        service providers, such as ArmCoil, to assist in
        choosing the correct strategic maintenance plan
        for the network. Specialist engineers and service
        providers can accurately pinpoint the unique
        requirements necessary for maximum output
        production and service provisions from plant to plant.
          Replacement strategies are not that complicated
        once all the information required is gathered. The
        return on investment enables strategic decisions   Based on the inspection results, which can take up to two weeks to be made available, in
        based on accurate information of the distribution   the worst-case scenario the unit is found to have the following defects:
        network equipment, which was derived from   •  Furan tests are below the minimum requirement (insulation levels indicate overloading)
        the preventive maintenance plan that the overall   Moisture content is above the acceptable levels
        strategic maintenance plan had in turn supported.  •  Dielectric results are below the minimum requirement
                                                 •  PCB content is high (this has no impact on the unit’s performance)
        Examining a hypothetical ArmCoil OSCA    •  The unit’s oil level is very low
        scenario                                 •  Tap-changer, breather, Buchholz relay, auxiliary equipment, radiators and gaskets are in
        Assume a 2000 kVA, 33 kV – 415 V distribution   need of replacement.
        transformer, manufactured in 1960 and currently
        in operation.                            Armed with the inspection report, over a period of one or two days, the corrective
          Assume there are no past maintenance   maintenance, as put forward by the experts, could include the following:
        records or historical staff knowledge of the   Instead of oil purification, the oil is replaced. This is done because the Furan results
        equipment – a common occurrence as staff are   are so poor, and the purification procedure could weaken the insulation and cause the
        promoted, retire or resign, etc.         embedded sludge to loosen up and settle on other areas, thereby possibly creating a
                                                 failure condition during energising.
        Initially, from a visual inspection, the following is   All recommended parts including gaskets are replaced except for the tap changer due
        noticed:                                 to shut down time restrictions. The tap changer is therefore temporarily short-circuited in
        •  Oil is leaking from the unit, which is evident from   the attempt to halt the fluctuation of supplied voltage.
         looking at the plinth                      Since thermal imagery shows blocked radiator fins and channels, it is decided to
        •  Heavily discoloured, there is no evidence of what   remove them and have them ‘flushed out’ on-site only. Replacement of radiators is
         colour the unit should be               delayed due to shut down time constraints.
        •  Rust is evident on the radiators, skids, conservator,   A follow-up inspection is scheduled to be conducted within a month to start the
         fasteners and piping                    preventive maintenance strategy, to predict failure or replacement of the unit. The above
        •  There is a continuous ‘buzz’ sound which   corrective maintenance strategy and documentation received places the unit’s owner
         increases during peak loads             in a proactive position to evaluate the unit in operation in terms of reaching its ‘end of
        •  When standing close to the unit, an ominous   service’ criteria. It is advisable to consult internally or externally on the requirements for
         odour is evident                        the replacement unit, as there are many variables to consider, which are unique to each
        •  The unit trips randomly due to high temperatures   network’s specifications.
         during operation                           Furthermore, before taking the route of rewinding transformers from 50 kVA to
        •  Staff report that the tap changer has not worked   3,5 MVA, time should be taken to compare repair costs with locally manufactured costs.
         for the past few months.                Also, compare the repair delivery period with the manufacturing delivery period: both
                                                 options have advantages and disadvantages for your network’s specifications. The cost
        There is a concern that this unit is unsafe and could   saving potential that can be achieved if the measures of maintenance strategies discussed
        ‘explode’ at any time. An inspection of the unit is   herein are implemented is, in general, not quantifiable. It depends on company-specific
        undertaken by a specialist to establish the corrective   factors such as input to increase efficiency or production, current maintenance strategies
        maintenance action required. The inspection covers   in practice, technical design of equipment and design of plant, network structure,
        the full range of oil sampling, thermal imagery of   topographic conditions and legal framework.        n
        the unit and cable joints, and full visual inspection
        of the unit whilst in operation – culminating in the   Contact Morné Bosch, ArmCoil, Phone 011 763-2351, morneb@armcoil.co.za,
        submission of a comprehensive inspection report.  www.armcoil.co.za



                                               energize | November/December 2021 | 5
   2   3   4   5   6   7   8   9   10   11   12