Page 53 - Energize April 2022
P. 53

TECHNICAL




































        Figure 3a                                  Figure 3b

        Test procedures                                           If a test voltage is applied that is greater than 120% of the
        The test must be done with consistency, so use the same test   arrester’s rated voltage, then it will result in a lower-than-expected
        voltage setting and apply the test voltage for the same amount of   resistance value even when the arrester is not faulty. Therefore, it
        time each time. It is recommended that the test voltage is applied   is best to stay within the recommended test voltage range of 50%
        for at least 15 s, but optimally 60 s. Repeat the test three times,   to 120% of the arrester’s rated voltage.
        taking the average reading as the result. A repeatable result is
        indicative of a good measurement process.              Test results and recommendations
           A good medium voltage (1 kV to 30 kV) arrester should have a   A test was done on a selection of 15,3 kV rated surge arresters.
        very high resistance of gigaohm to terohm range at its operating   The test parameters were:
        voltage range and arresters of the same type and voltage rating   •  15 kV applied test voltage
        should have very similar resistance values. Any arrester that   •  30 seconds of applied test voltage each time
        shows a low resistance value is faulty and must be replaced or   •  No filters or special settings used
        refurbished.                                           •  3 tests were done on each arrester, but only after fully
                                                                 discharging each time
                                                               •  Pass/Fail level was determined to be 1 GΩ based on
                                                                 manufacturer’s information

                                                               It is highly recommended to check surge arresters regularly. The
                                                               test for them is simple and quick, and it needs to be done. A faulty
                                                               arrester can result in severe damage to expensive assets, like
                                                               transformers. Therefore, regularly following the simple process
                                                               from this application note can save money and maintain a smooth
                                                               and steady electric power supply.

                                                               Contact Marie-Claude Rasendra, Megger,
        Figure 4                                               Marie-Claude.Rasendra@megger.com, www.megger.com

        Arrester ID        Test 1 (MΩ)      Test 2 (MΩ)       Test 3 (MΩ)      Average (MΩ)      Result
        12001              839              919               909              889               FAIL
        12003              1115             1212              1206             1178              PASS
        12004              1190             1174              1146             1170              PASS
        12008              999              1066              1038             1034              PASS
        Table 1: Surge arrester test results



                                                    energize | April 2022 | 51
   48   49   50   51   52   53   54   55   56   57   58