                                                              •  Fault detection, in its most basic form, is achieved by a current
                                                                transformer which feeds the switch directly or via the control device.
                                                                Current transformers are fitted on the outgoing side of the switch.
                                                              •  The switch operating mechanism is used to close the switch and may
                                                                also be used to open the switch from a remote signal.
                                                              •  The controller is used to control the operation of the reclose and
                                                                lockout cycle.
                                                              •  Communications, monitoring and recording devices are fitted to
                                                                the more modern types. These allow communication with a central
                                                                control site as well as other reclosers; they record voltage and
                                                                current levels and other relevant data.
                                                              •  Sensing and monitoring devices monitor voltage, current and other
                                                                parameters.

                                                              The intelligent recloser offers a number of additional monitoring and
                                                              protection features which make managing the network easier. Most
                                                              reclosers offer the following features:
                                                              •  Trip functions
                                                                - Phase over current
                                                                - Earth fault
                                                                - Sensitive earth fault (SEF)
                                                              •  Trip or alarm only
                                                                - Under/over voltage
                                                                - Under/over frequency
                                                                - Rate of change of frequency
                                                                - Neutral voltage displacement
                                                                - Broken conductor
                                                                - Loss of phase

                                                              The following functions can be provided in addition to basic functions
                                                              •  Inrush restraint (zero detect/2nd harmonic)
                                                              •  Directional protection
                                                              •  Directional blocking
        Figure 1: Typical recloser and control unit (Schneider)   •  Fault location



































        Figure 2: Stand-alone and networked recloser           Figure 3: Typical recloser structure (ABB)