Page 50 - Energize August 2022
P. 50

TECHNICAL


        Recloser versions
        Single-phase
        Single-phase ARCs are used to protect single-phase lines such as
        branches or taps of a three-phase feeder. They can also be used on
        three-phase circuits where the load is predominantly single-phase.   Figure 4: ARC operation to lockout
        When a permanent phase-to-ground fault occurs, one phase can be
        locked-out while service is maintained to the remaining phases.
           Single-phase reclosers can be controlled by means of a hydraulic
        control (integrated within the recloser tank), or an electronic control
        (housed in a separate enclosure) based upon the recloser design.
                                                               Figure 5: ARC operation to power restoration
        Three-phase
        Three-phase reclosers are used on three-phase circuits to improve
        system reliability and where lockout of all three phases is required for
        any permanent fault, to prevent single phasing of three-phase loads
        such as large three-phase motors.

        Three modes of operation are commonly used:
        •  Three-phase trip and three-phase lockout: For any fault (single-
          phase-to-ground, phase-to-phase or three-phase), all contacts
          open simultaneously for each trip operation. The three phases,
          mechanically linked together for tripping and reclosing, are operated   Figure 6: Protection curves available (Schneider)
          by a common mechanism.
        •  Single-phase trip and three-phase lockout: Each phase operates   ionised gas caused by the lightning strike or flashover to dissipate,
          independently for overcurrent tripping and reclosing. If any phase   typically 2 seconds or less. If this first reclose is too quick, the ionised
          sequences to lockout condition (due to permanent fault), or if   gas could cause a restrike of the fault.
          lockout is locally or remotely asserted, the other two phases trip   If the ARC recloses onto a fault it is fairly certain that the fault
          open and lock out. Extended single-phase energisation of three-  was not caused by lightning, and most likely by contact with the
          phase loads is prevented.                            conductors. The second and third trips are usually slower inverse
        •  Single-phase trip and single-phase lockout: Each individual phase   time delay curves, which allow fault current to quite literally burn the
          trips and sequences to lockout independent of each other. This   fault off the network. These inverse time curves trip faster on higher
          is primarily for residential loads and/or where single-phasing of   fault currents and slower on low fault currents, effectively acting as
          three-phase loads is protected by other means. Phase-selective   an equipment stress threshold which allows for the maximum energy
          relays must be used to control the tripping and the recloser requires   to be delivered to a fault so as to burn off the fault without causing
          individual closing/tripping mechanisms for each phase. As a   physical damage to the network.
          result, the single-phase option is more complex and usually more   The second and third reclose times typically tend to be longer (in
          expensive.                                           the 5 to 10 second range), allowing time for the incinerated debris
                                                               to fall away from the line1. If a reclose sequence makes it past the
        Recloser operation                                     third trip, the fault is likely to be a permanent bolted fault, at which
        Upon detecting a fault, the ARC will open and remain open for a   point reclosing does very little anymore and field service becomes
        period known as the dead time. At the end of the dead time the ARC   necessary.
        will reclose. If the fault persists, the ARC will re-open and remain open   In city areas where buildings are higher than power lines, the
        for a second dead time. If the fault still persists, the ARC will lock out   most common transient fault is more likely to be a foreign body on
        after the last trip. If the fault clears before the last trip cycle is reached,   the network or a fallen conductor. In built up areas, the most common
        the ARC remains closed and restores power to the network.   deployment is a three shot to lockout system with a first fast trip. The
           The ARC may be set to lock out after fewer than four trips,   reclose times are in line with what is deployed in the rural lines.
        and both the dead time and the trip time may be set to suit local   In the case of SEF in urban areas, the ARC is usually set to a single
        conditions. Operation is limited a total of four trips, and three recloses.   shot to lockout. This is due to the likelihood of SEF being triggered
        Dead time is chosen to allow the fault to clear. Dead time is based on   by conductors lying on the ground, and this risk is much higher in an
        the expected type of fault to be cleared. The ARC will have the option   urban environment.
        of a number of different tripping curves, and trip time may be selected
        to follow any standard fuse or circuit breaker curve or user-defined   Sectionalisers
        curve.                                                 Unlike a recloser, a sectionaliser does not have the capability to
           In a rural overhead network, lightning is the most common fault,   break fault current. A sectionaliser is a device which automatically
        followed by vegetation contacts, so the first trip is typically as fast as   isolates faulted sections of a distribution circuit, once an upstream
        possible. This is to interrupt the fault before damage is caused to the   breaker or recloser has interrupted the fault current and is usually
        network. The following dead time needs to be long enough for the   installed downstream of a recloser.



                                                   energize | August 2022 | 48
   45   46   47   48   49   50   51   52   53   54   55