Page 33 - Energize April 2021
P. 33

TECHNICAL



        or based on GE’s design criteria, such as corona rings, top hats,   •   Design/manufacturing capabilities. The size of a shunt
        elevating structures, line/grounding connectors, etc.     reactor depends primarily on its inductance and current;
                                                                  the higher the inductance and/or the current, the bigger
        Application of shunt reactors                             the coils. For very low reactive power, the inductance may
           The main functions of shunt reactors in transmission and   be extremely high, which may exceed the manufacturing
        distribution systems are:                                 capabilities (maximum diameter x height of the winding
        •   Control of operating voltages                         machines). For very high reactive power, the current may be
        •   Support of reactive power compensation                extremely high, requiring a huge aluminium mass to achieve
        •   Reduction of switching transients on transmission lines   a desirable temperature increase and/or losses dissipation. In
                                                                  both cases, the selection of a properly rated voltage for the
        Shunt reactors can be installed at both transmission and distribution   shunt reactor may eliminate or minimize the impacts on the
        grids, being directly connected to substation busbars, transmission   reactor’s design and manufacture.
        line endings and to the tertiary windings of large power transformers,   •   Rated voltage and power of the tertiary winding, for tertiary
        as shown in Figure 2.                                     reactors. Therefore, the reactive power of a shunt reactor
                                                                  depends heavily on its operating voltages.

                                                               The typical ranges of reactive power (three-phase basis) for each
                                                               system voltage that result in feasible and competitive dry type air
                                                               core shunt reactors are presented below:
                                                               •   15 kV and below: 0,5 Mvar to 25 Mvar
                                                               •   25 kV and 38 kV: 2,5 Mvar to 60 Mvar
                                                               •   72,5 kV: 5 Mvar to 100 Mvar
        Figure 2: Shunt reactor application in power systems
                                                               •   138 kV: 7,5 Mvar to 150 Mvar
                                                               •   245 kV: 20 Mvar to 200 Mvar
        The rated voltage and reactive power of a shunt reactor, as well its   •   345 kV and 400 kV: 50 Mvar to 250 Mvar
        location, are normally determined by system studies, such as load   •   500 kV: 100 Mvar to 350 Mvar
        flow and transients. Moreover, the ratings of shunt reactors also
        depend on the following factors:                       For reactive power other than the above-mentioned ranges, the
        •   Current and voltage capabilities of the switching devices. The   manufacturer should be consulted to determine technical feasibility.
           introduction of inductive currents may create severe transient
           voltages (TRV) over the shunt reactor and across the switching   Protection and grounding
           devices. The magnitude and rate-of-rise of the TRV depends on   In most applications of shunt reactors in EHV and HV systems,
           the shunt reactor’s inductance and stray capacitances which   the star points of the reactors are connected to earth, whereas
           in turn depend on the voltage, reactive power, grounding, and   MV shunt reactors are generally not grounded. If the star point of
           construction of the shunt reactor. A typical TRV associated with   the transformer tertiary winding is not earthed, then grounding the
           the switching off of the shunt reactor is around 1,7 to 2,0 p.u. of   reactor would assist in detecting earth faults in this zone.
           the rated voltage.                                     However, such ground fault detection can also be made by
        •   Connection and grounding type of the shunt reactor. Most shunt   means of voltage measurement, with a grounded star primary and
           reactors are connected in star (or wye), being ungrounded for   open delta secondary voltage transformer used to detect ground
           system voltages of 72,5 kV and below and grounded for system   faults on the network supplied by the tertiary winding. Shunt
           voltages of 115 kV and above. For line reactors, when single-  reactors should be equipped with over-current and earth fault
           phase auto-reclosing of transmission lines is required, shunt   protection monitoring for the line side current.
           reactors can be grounded by a neutral reactor or resistor. The   In cases where the reactors are connected to the tertiary
           neutral grounding reactor can also be a dry type air core reactor,   winding of a transformer, it is most likely that the reactor feeder
           with similar construction to the shunt reactors. There are very   will be included in the transformer-differential protection.
           few cases of delta-connected shunt reactors, mainly related to   Differential protection of the reactor can be achieved by splitting
           industrial applications (Figure 3).                 each phase into two legs and monitoring the unbalanced
                                                               current in the star point.
                                                                  This method provides extremely fast and sensitive protection
                                                               of the reactor’s windings, especially in terms of inter-turn faults but
                                                               requires special coils design (split-phase reactors).


                                                               Switching of reactors
                                                               IEEE C37.015 provides comprehensive guidelines for the switching
                                                               requirements of shunt reactors. One of the most important aspects
                                                               of switching reactors is current chopping, caused by forcing the
                                                               reactor current to zero before the zero crossing. This could result
                                                               in high voltage across breaker poles. The introduction of copper/
                                                               chromium contact material in vacuum circuit breakers overcomes
        Figure 3                                               the problem of over-voltages as a result of switching, provided



                                                    energize | April 2021 | 31
   28   29   30   31   32   33   34   35   36   37   38