Page 58 - Energize August 2021
P. 58

TECHNICAL



           Extreme overloads can result in
        catastrophic transformer failure. The
        temperature of the top oil should
        never exceed 100°C for power
        transformers with 55°C insulation or
        110°C for those with 65°C insulation.
        The consequence of exceeding these
        limits could be oil overflow, excessive
        pressure, or tank rupture.
           If winding hot spot temperatures
        exceed 140°C when moisture is
        present, free bubbles may form and
        result in internal faults. Due to these
        considerations, the peak short duration
        loading of power transformers less than
        100 MVA should never exceed 200% of
        the nameplate rating.
           The resulting fault current passes
                                             Figure 1: Distribution transformer at substation
        through the transformer and shakes
        the windings with a mechanical force
        proportional to the square of the fault
        current magnitude. If thermal aging
        has caused the insulation to become
        sufficiently brittle, a crack will form and an
        internal transformer fault will result.
           Low impedance transformers
        tend to fail more often than high
        impedance transformers since they will
        experience more severe fault currents.
        Autotransformers generally have very low
        impedances and tend to fail more often
        than multiple-winding transformers.
           Extensive research has been done
        in the area of transformer condition
        assessment. The goal is to determine
        the health of the transformer and
        identify incipient problems before they
        lead to catastrophic failure. Simple
                                             Figure 2: Expected transformer life vs. hot spot temperature
        methods include visual and audio
        inspection. More complex methods
        include thermal load tests, power factor   pumps, fans and blocked radiators reduce the ability of transformers to dissipate heat but
        tests, high potential tests and dissolved   do not cause outages directly. Other failures, like cracked insulators and broken seals, may
        gas analysis, and other electrical,   result in outages but can be fixed quickly and inexpensively. Oil-filled load tap changers have
        mechanical, and chemical techniques.  historically been prone to failure and can substantially reduce the reliability of a transformer.
           Some of these tests can be performed   Manufacturers have addressed this problem so that new devices using vacuum
        continuously, referred to as condition   technology have succeeded in reducing load tap changer failure rates.   n
        monitoring and can automatically notify
        operators if monitored values exceed   Acknowledgement
        warning thresholds.                  This article was first published by Electrical Engineering Portal
           Transformers have many accessories
        that can also fail. Failures associated with   Send your comments to rogerl@nowmedia.co.za

















                                                   energize | August 2021 | 56
   53   54   55   56   57   58   59   60