Page 57 - Energize August 2021
P. 57

TECHNICAL

        Common failure modes of



        distribution electrical equipment





        by Edvard Csanyi, EEP





            ach piece of electrical equipment
                                              Temperature                   55°C rise insulation   65°C rise insulation
            on a distribution system has a
       Eprobability of failing. When first
                                              Ambient temperature           30°C               30°C
        installed, a piece of equipment can fail due                                                                    n
        to poor manufacturing, damage during   Average winding temperature rise   +55°C        +65°C
        shipping, or improper installation. Healthy
        equipment can fail due to extreme currents,   Average winding temperature   85°C       95°C
        extreme voltages, mischievous animals,
                                              Additional hot-spot temperature rise   +10°C     +15°C
        severe weather and many other causes.
           Sometimes equipment will fail      Hot-spot temperature          95°C               110°C
        spontaneously for reasons such as
                                             Table 1: Temperatures used for transformer ratings
        chronological age, thermal age, state
        of chemical decomposition, state of
        contamination and state of mechanical   The rate of breakdown increases exponentially with temperature, allowing the expected
        wear. The following paragraphs in this   life of insulation to be expressed by the Arrhenius theory of electrolytic dissociation: insulation
        technical article present the most common   life = 10 (K1/(273+°C)) + K2  hours
        modes of failure for equipment that is most   Constants for this equation have been experimentally determined for both power
        critical to distribution system reliability.  transformers and distribution transformers and are documented in standard transformer
           Transformers impact distribution   loading guides.
        system reliability in two related ways:   A summary of these values is shown in Table 2. This table also shows the required hot
        failures and overloads. Catastrophic   spot temperature rise above normal limits that will cause the rate of thermal aging to double.
        transformer failures can result in     Many older transformers have 55°C rise insulation, but most new transformers have 65°C
        interruptions to thousands of customers.   rise insulation. Higher insulation ratings allow transformers to operate at a higher temperature
        When this happens, other transformers   and, therefore, serve higher loads.
        are often called upon to pick up the   Plots of life versus hot spot temperature are shown in Figure 1. These curves can be
        interrupted load.                    used to determine the expected life of a transformer and to estimate the loss of life that will
           If there is not enough spare transformer   occur during an overload. If run constantly at hot spot design temperatures (95°C for 55°C
        capacity, a decision must be made    insulation and 110°C for 65°C), power transformers have an expected insulation half-life of
        whether or not to overload in-service   about 7,2 years and distribution transformers have an expected insulation half-life of about
        transformers and accept the resulting   20 years.
        loss of life. Accepting loss-of-life will   Transformers are not normally loaded constantly at their nameplate rating and are re-rated
        improve reliability for the moment but will   by utilities based on weekly load curves to result in an acceptable lifetime (e.g., 30 years).
        increase the probability that the overloaded   Loss-of-life will occur if the temperature is allowed to rise above normal ratings, and many
        transformers will fail at a future date.  utilities will accept a certain amount of loss-of-life during emergency situations.
           A summary of transformer design     Typical transformers are designed for hot spot temperatures of 95°C (55°C rise
        temperatures is shown in Table 1.    insulation) or 110°C (65°C rise insulation). Transformer life reduces exponentially with hot
           Older 55°C rise transformers are shown   spot temperature.
        to have a hot spot design temperature of
        95°C and newer 65°C rise transformers
        are shown to have a hot spot design   Description               K1      K2      Rise which doubles ageing rate
        temperature of 110°C.
           The life of a transformer is often   Power transformer (+55°C)   6972,15   -14,133   95°C + 5,9°C
        defined as the time required for the
                                              Power transformer (+65°C)   6972,15   -13,391   110°C + 6,4°C
        mechanical strength of the insulation
        material to lose 50% of its mechanical   Distribution transformer (+55°C)   6328,80   -11,968   95°C + 6,6°C
        strength (many other definitions are also
        possible). Loss of mechanical strength   Distribution transformer (+65°C)   6328,80   -11,269   110°C + 7,1°C
        occurs when insulation polymers break
                                             Table 2: Transformer aging constants for insulation equation above, determined by accelerated aging tests
        down due to heat.                    that measure the time required for transformer insulation to lose 50% of its initial strength


                                                   energize | August 2021 | 55
   52   53   54   55   56   57   58   59   60