Page 57 - Energize August 2021
P. 57
TECHNICAL
Common failure modes of
distribution electrical equipment
by Edvard Csanyi, EEP
ach piece of electrical equipment
Temperature 55°C rise insulation 65°C rise insulation
on a distribution system has a
Eprobability of failing. When first
Ambient temperature 30°C 30°C
installed, a piece of equipment can fail due n
to poor manufacturing, damage during Average winding temperature rise +55°C +65°C
shipping, or improper installation. Healthy
equipment can fail due to extreme currents, Average winding temperature 85°C 95°C
extreme voltages, mischievous animals,
Additional hot-spot temperature rise +10°C +15°C
severe weather and many other causes.
Sometimes equipment will fail Hot-spot temperature 95°C 110°C
spontaneously for reasons such as
Table 1: Temperatures used for transformer ratings
chronological age, thermal age, state
of chemical decomposition, state of
contamination and state of mechanical The rate of breakdown increases exponentially with temperature, allowing the expected
wear. The following paragraphs in this life of insulation to be expressed by the Arrhenius theory of electrolytic dissociation: insulation
technical article present the most common life = 10 (K1/(273+°C)) + K2 hours
modes of failure for equipment that is most Constants for this equation have been experimentally determined for both power
critical to distribution system reliability. transformers and distribution transformers and are documented in standard transformer
Transformers impact distribution loading guides.
system reliability in two related ways: A summary of these values is shown in Table 2. This table also shows the required hot
failures and overloads. Catastrophic spot temperature rise above normal limits that will cause the rate of thermal aging to double.
transformer failures can result in Many older transformers have 55°C rise insulation, but most new transformers have 65°C
interruptions to thousands of customers. rise insulation. Higher insulation ratings allow transformers to operate at a higher temperature
When this happens, other transformers and, therefore, serve higher loads.
are often called upon to pick up the Plots of life versus hot spot temperature are shown in Figure 1. These curves can be
interrupted load. used to determine the expected life of a transformer and to estimate the loss of life that will
If there is not enough spare transformer occur during an overload. If run constantly at hot spot design temperatures (95°C for 55°C
capacity, a decision must be made insulation and 110°C for 65°C), power transformers have an expected insulation half-life of
whether or not to overload in-service about 7,2 years and distribution transformers have an expected insulation half-life of about
transformers and accept the resulting 20 years.
loss of life. Accepting loss-of-life will Transformers are not normally loaded constantly at their nameplate rating and are re-rated
improve reliability for the moment but will by utilities based on weekly load curves to result in an acceptable lifetime (e.g., 30 years).
increase the probability that the overloaded Loss-of-life will occur if the temperature is allowed to rise above normal ratings, and many
transformers will fail at a future date. utilities will accept a certain amount of loss-of-life during emergency situations.
A summary of transformer design Typical transformers are designed for hot spot temperatures of 95°C (55°C rise
temperatures is shown in Table 1. insulation) or 110°C (65°C rise insulation). Transformer life reduces exponentially with hot
Older 55°C rise transformers are shown spot temperature.
to have a hot spot design temperature of
95°C and newer 65°C rise transformers
are shown to have a hot spot design Description K1 K2 Rise which doubles ageing rate
temperature of 110°C.
The life of a transformer is often Power transformer (+55°C) 6972,15 -14,133 95°C + 5,9°C
defined as the time required for the
Power transformer (+65°C) 6972,15 -13,391 110°C + 6,4°C
mechanical strength of the insulation
material to lose 50% of its mechanical Distribution transformer (+55°C) 6328,80 -11,968 95°C + 6,6°C
strength (many other definitions are also
possible). Loss of mechanical strength Distribution transformer (+65°C) 6328,80 -11,269 110°C + 7,1°C
occurs when insulation polymers break
Table 2: Transformer aging constants for insulation equation above, determined by accelerated aging tests
down due to heat. that measure the time required for transformer insulation to lose 50% of its initial strength
energize | August 2021 | 55