Page 52 - Energize October 2021
P. 52

TECHNICAL


       Pinpointing concealed problems inside a



       resistive-type OLTC before physical inspection



        A case study by Megger




            he following experience centred on a seventeen-position
            resistive-type on-load tap changer (OLTC) which is installed
        Ton the HV side of a three-phase YNd1, 25 MVA, 132/11,5 kV
        transformer. This load tap-changing transformer is operated by Electric
        Power Transmission Network in the City of Karbala, Iraq.
           A systematic procedure of off-line testing techniques, including
        dynamic resistance measurement (DRM), identified internal damage of   Table 1
        the OLTC. After repair, a verification testing protocol assured the OLTC’s
        successful restoration to a normal and safe operating condition, as
        evidenced by the DRM graphical and numerical response.
           The maintenance team at the Electric Power Transmission
        Network in the City of Karbala performed routine electrical tests on
        the transformer including winding resistance measurements (WRM),
        transformer turns ratio (TTR), short circuit impedance (SCI), excitation
        current and line-frequency power factor (also known as dissipation
        factor or tan delta).
           The maintenance team’s TRAX instrument afforded the opportunity
        to complete advanced testing also, including magnetic balance,
        frequency response of stray losses (FRSL) and OLTC dynamic resistance
        measurement (DRM) tests.                               Figure 1: WRM results for all 17 taps and all three phases
           Only the DRM test results clearly flagged a deficiency in Phase B
        of the OLTC, which was not observed in static measurements. Static
        measurements are those that are performed while the OLTC (and
        DETC) is stationary at each of a number of selected tap positions.
        Examples of tests that provide static tap changer measurements
        include excitation current, TTR, WRM and sweep frequency
        response analysis (SFRA).
           Dynamic tap changer measurements, such as provided by a DRM
        test, are critical to assess a resistive-type OLTC’s bridging or ‘transition’
        components, which only appear in a test circuit during the OLTC’s
        transition from one tap position to the next. A resistive-type OLTC
        does not use its bridging state as a viable tap service arrangement/
        position, so these components never appear in the test circuit of a
        static measurement.
                                                               Figure 2
        Test results
        In this case, the DC WRM on all tap positions (a series of static
        measurements, Figure 1) shows a very small variation (around 0,2
        %) between the three phases and for all taps. This is well within the
        generally agreed, maximum allowable variation of 2 to 3%.
           Looking at the TTR measured values (Figure 2), it was observed
        that all phases and all taps have a measured ratio well within the
        generally agreed acceptance value of 0,5%
           The line-frequency (LF) power factor (PF), or dissipation factor
        (DF), and NB DFR (narrowband dielectric frequency response) test
        results (Table 1 and Figure 3) were acceptable. No notable insulation
        degradation was indicated.
           Advanced OLTC testing was carried out with the dynamic resistance
        measurement application in the TRAX SW. During the transition from
        one tap position to the next, the current drops and that is represented   Figure 3



                                                   energize | October 2021 | 50
   47   48   49   50   51   52   53   54   55   56   57