Page 60 - Energize October 2022
P. 60

TECHNICAL



        at different stages of the conversion to produce a clean sinusoidal waveform.   to maintain inertia.
           Figure 1 shows the typical inverter stages. The AC output is achieved by turning on/  Generator sets selection should
        off the IGBTs at a pre-defined sequence and speed which generates pulses of currents   consider the fuel available at the project
        which is known as modulation, see Figure 2. There are multiple modulation techniques   location, the expected usage, emissions
        such as pulse-width (PWM), pulse-frequency and pulse-amplitude modulation. PWM   requirements, noise limitations, and
        inverters are the most common as they eliminate lower order harmonics and decrease   the microgrid’s configuration. There are
        the total harmonic distortion (THD) content in the output AC voltage.     many different generator technologies
           Inverters can be grid-forming or grid-following. In grid-following, a voltage reference   available on the market that can
        must be established by another AC energy source such as the utility or a generator set   meet the needs to microgrids. The
        before the inverter is able to synchronise and connect to the network.    two most common concerns when
           In grid-forming inverters, the inverter does not require a reference voltage and can   using generator sets for microgrids
        establish the voltage of the network independently. Solar inverters are most commonly   and prime applications are noise and
        grid-following, whereas storage inverters can be either grid-forming, grid-following or   emissions, with increasing pressure
        both.                                                                     to be environmentally and socially
                                                                                  responsible.
        Synchronous machines                                                        Modern generator sets are available
        Generator sets                                                            with exceptionally low emissions due to
        While PV panels and batteries are DC power devices, most electrical equipment uses AC   advancements in combustion and after-
        power. A generator set, by its nature, generates AC power and can directly be used to   treatments technologies. Additionally,
        power AC loads on demand, and can be paralleled with other AC power sources such as   low carbon fuels such as renewable
        the utility grid.                                                         natural gas (RNG) and biogas can be
           Incorporating a synchronous machine into a microgrid application has many benefits.   used for carbon neutral operation.
        A generator set is a dependable, dispatchable energy source which, if fuel is available   Noise can be addressed through
        can be used to meet the electrical load demand. Generators, with their high-power   highly sound-attenuated enclosures and
        density, can start quickly, accept large block loads, and provide a reference to grid   buildings. Noise and emissions at the
        following components such as PV or battery inverters.                     site level can also be minimised through
           With intelligent controls in modern generator sets, autonomous synchronisation   intelligent controls which optimise
        and load sharing can be done at the equipment level and there are a wide variety   the use of each asset to minimise the
        of generator sets available at various power levels that accept different fuel types.   duration and timing of the operation.
        Generator sets provide inertia to a system that inverter-based generation cannot
        provide, contributing to the overall stability of the system.             Paralleling AC power sources
           Some microgrids, consisting of synchronous generators and PV energy for example,   To parallel or connect alternating power
        will require a minimum capacity of synchronous generators to be operating at all times   sources, several characteristics of the
                                                                                  AC output voltage must be the same or
                                                                                  within an acceptable range. It is essential
                                                                                  that the waveform and phase sequence
                                                                                  are the same. Also, the frequency, phase
                                                                                  angle and voltage amplitude must be
                                                                                  within the acceptable range to safely and
                                                                                  effectively parallel the AC sources.
        Figure 1                                                                    Synchronous generator sets produce
                                                                                  AC voltage and can be either in load
                                                                                  sharing (analogous to grid-forming)
                                                                                  or in load governing mode (analogous
                                                                                  to grid-following) which are the terms
                                                                                  used to describe the generator set
                                                                                  paralleling functions. Load sharing is the
                                                                                  proportional division of kW and kVAR
                                                                                  total load among multiple generators in
                                                                                  a paralleled system.
                                                                                    Load sharing is essential to avoid
                                                                                  overloading and stability problems on
                                                                                  the paralleled generator sets. In load
                                                                                  sharing the generator sets regulate their
        Figure 2                                                                  voltage and frequency. Load sharing can



                                                   energize | October 2022 | 60
   55   56   57   58   59   60   61   62   63   64   65