Page 61 - Energize October 2022
P. 61

TECHNICAL



        either be isochronous (where voltage
        and frequency stay constant at a 100%
        regardless of the load) or droop (where
        the voltage and frequency vary as the
        load varies).
           The advantage of isochronous
        load sharing is the constant voltage
        and frequency; however, it requires
        the sources to communicate with
        each other. On the other hand, droop
        does not require communication
        interconnection between the power
        sources at the expense of varying
        voltage and frequency as the load
        varies. The load govern function applies
        when a generator set, or multiple sets   Figure 3
        are paralleled to a utility or the grid.
           Because the utility voltage and   paralleling control and it can either be isochronous, the most common and preferred
        frequency are fixed, the generator sets   method or droop as described earlier.
        regulate their kW and kVAR output,     When it comes to load sharing with inverters, one method would be to set the
        instead of their frequency and voltage.   generator sets to operate as the utility (load sharing/grid forming), and the inverters
        It is expected that the synchronous   would operate in grid following and act like a constant real-reactive power (PQ) source.
        generator onboard paralleling controls   An external control system would send these PQ commands to the inverter.
        have paralleling and protection
        capabilities built in.               Microgrid controller
                                             At the heart of any microgrid power system there must be an autonomous controller
        The generator sets’ paralleling control   (Figure 4). The microgrid controller is expected to do, as a minimum, the following:
        is typically responsible for all the   •  Optimise energy production from all energy sources to meet demand
        following:                           •  Maximise the output power of renewable sources
        •  Paralleling functions             •  Control loads via load add and load shed
        •  First start arbitration           •  Minimise emissions and fuel consumption
        •  Synchronising (phase angle,       •  Achieve the lowest levelised cost of energy (LCOE) and total cost of ownership (TCO)
           voltage, frequency)                 for all assets
        •  Load sharing (kW and kVAR)
        •  Protection
        •  Metering
        •  Alarms
        •  Built-in safe manual paralleling

        When it comes to renewable energy
        sources and battery storage units, the
        output voltage is DC and therefore an
        inverter will be used to invert the DC
        into AC, see Figure 3.
           Typically, photovoltaic inverters
        are grid-following whereas storage
        inverters can be both grid-forming
        and/or grid-following. Inverters
        are responsible for the lower-level
        synchronisation, protection and
        metering. However, one essential
        aspect when paralleling is load sharing
        across all the sources. Load sharing
        across synchronous generators is
        simply accomplished via the on-board   Figure 4



                                                   energize | October 2022 | 61
   56   57   58   59   60   61   62   63   64   65   66