Figure 5: Voltage based timing measurement (Megger)

        verifying that the breaker operates within specified operation parameters. Standard test   and logs the following information during
        voltage is 85% (and 70%) of nominal voltage for close (and open). 5       circuit breaker operation:
           The value of the operating voltage affects the operation of the coil as shown in Figure 6.  •  Trip time (ms) (also known as opening
                                                                                   time)
        On line monitoring system for switchgear testing                          •  Arc duration (ms) (phase segregated)
        Online testing and monitoring allows the performance to be measured in-circuit. There are   •  Clearing time (ms) (also known as
        some test and performance test methods which are easier to perform online than using test   interrupting time)
                                                                                            2
        apparatus. Online monitoring gives an indication of the performance of the switch under real   •  Cumulative I T or IT on the main
        operating conditions, and can provide information not available with online testing.   contacts (phase segregated) from arcing
                                                                                  •  Restrike occurrence (phase segregated)
        Breaker performance monitoring is ideally suited for implementing predictive maintenance,   •  Operation counts
        maintenance deferral, condition-based maintenance and increased environmental protection
        from SF6 gas leaks. It monitors the condition of the main contacts, mechanism and dielectric,   References
                                                                                  1. D Genutis: “Top five switchgear failure causes”,
                                                                                   NETAWorld, 2010.
                                                                                  2. T Raudon: “On-site non-intrusive testing of
                                                                                   AC circuit-breakers”, CIGRÉ A3-069, CIGRÉ,
                                                                                   Winnipeg 2017 Colloquium.
                                                                                  3. A Subramanium, et al: “Switchgear condition
                                                                                   assessment and lifecycle management:
                                                                                   standards, failure statistics, condition
                                                                                   assessment, partial discharge analysis,
                                                                                   maintenance approaches, and future trends”,
                                                                                   IEEE electrical insulation magazine, April 2021.
                                                                                  4. G Paoletti, et al: “Failure contributors of mv
                                                                                   electrical equipment and condition assessment
                                                                                   program development”, IEEE Transactions on
                                                                                   Industry Applications, December 2002.
                                                                                  5. Megger: “Recommended circuit breaker tests”,
                                                                                   https://megger.com//applications/circuit-
                                                                                   breakers/recommended-circuit-breaker-tests.

                                                                                  Send your comments to
        Figure 6: Coil current profile for different voltage from 0,25% to 1,25% of nominal voltage 3  rogerl@nowmedia.co.za



                                                    energize | June 2022 | 50