Page 49 - Energize June 2022
P. 49

TECHNICAL



           The best way to gather information   values. In view of this, the test results should only be interpreted for comparative purposes.
        about the condition of a circuit breaker   This does not indicate the quality of the primary insulation system from the point of view of
        would be to take it out of service and   dielectric withstand-ability.
        subject it to a comprehensive battery of
        tests. Taking a breaker out of service for   Contact resistance measurement
        testing almost always presents challenges,   Contact resistance (CR) measurement can give an indication of the state of the contacts,
        given today’s pressing uptime demands   both during static and operational states, obviating the need for visual inspection of the
        and limited maintenance resources.   contacts and opening of the switch enclosure. CR measurement is conducted at the normal
        Offline testing requires the removal of   current rating of the switch but using a DC source. Contact resistance is very low and is
        the switch from service and an intrusive   measured using a micro-ohm (μΩ) meter. It is recommended that for MV the resistance
        test and examination of components. The   test be made with 100 A or higher DC. The use of a higher current value gives more reliable
        test is time-consuming and is usually only   results than using lower current values.
        undertaken if other non-intrusive tests
        indicate problems.                   Static resistance measurement
           Online testing comprises a set of   Static resistance measurement is conducted with the switch contacts in the closed position.
        non-intrusive tests undertaken with the   The resistance is measured using a micro–ohm meter and a high current source. Contact
        breaker in service but isolated from both   resistance is measured by injecting a known DC current through the main contact system when
        the supply and feeders, as well as being   the circuit breaker is closed. By measuring the voltage drop, the resistance can be calculated.
        earthed at both points. Online tests do   The value of the main contact resistance reflects the condition of the conducting parts.
        not provide the same level of information   The static resistance value provides a reference value for all types of electrical contacts
        as offline tests but can indicate whether   and joints. The international standard IEC 56 states that this resistance is to be measured
        offline testing or maintenance is required.  using a current between 50 A and the breaker’s nominal current. Other international and
           Monitoring requires the permanent   national standards set forth similar guidelines in order to eliminate the risk of obtaining
        installation of measuring equipment on   erroneously high measurements if the test current is too low. In some cases, heat generated
        the switch. Such equipment is used to   by a high test current disperses any contact grease remnants or other impurities found on
        measure and record the performance of   contact surfaces (resulting from numerous high-current breaking operations). When the
        the switch under real operating conditions.   circuit breaker contacts are in poor condition, the values obtained can differ dramatically
        Monitoring the switch performance    from those measured at factory when the breaker was new. 3
        under real operating conditions may
        reveal different results from online test   Dynamic resistance measurement (DRM)
        conditions.                          This test is conducted by injecting DC current through the breaker main contacts and
                                             measuring both the voltage drop and the current while the breaker is operated. These values
        Non-intrusive test methods that are   are then used to plot the resistance as a function of time. If contact movement is recorded
        typically performed on-site include:  simultaneously, it is possible to determine the resistance at each contact position. This
        •  Insulation resistance test        method is used mainly for contact diagnosis, but can also be used for main contact timing.
        •  Static resistance measurement       With DRM, the arcing contact length can be reliably estimated as shown in Figure 2.
        •  Timing analysis and coil current analysis  The only alternative way of finding the length of the arcing contact is to dismantle the
        •  Motion analysis,                  circuit breaker. In SF6 breakers the arcing contact is commonly made of tungsten.
        •  Motor current
        •  Dynamic resistance measurements

        Insulation resistance measurement test
        The insulation resistance is measured
        using a megohmmeter, which applies a
        voltage of between 600 and10 000 V DC
        to the switch to determine the value of
        its resistance but does not indicate the
        quality of the primary insulation.
           Several factors should be remembered
        when performing this test: The first is
        that this test can indicate low values of
        insulation resistance because of many
        parallel paths, and the other is that an
        insulation system having low dielectric
        strength may indicate high resistance   Figure 2: Dynamic resistance measurement (Megger)



                                                    energize | June 2022 | 47
   44   45   46   47   48   49   50   51   52   53   54