Page 58 - Energize June 2022
P. 58

TECHNICAL



        Colour and appearance: This routine inspection is applied to   water content can cause flashover in the unit, resulting in loss of
        every oil sample. When an oil sample arrives at the laboratory,   the asset.
        one of the “tests” is a visual inspection of the oil sample in a
        clear vessel to determine the colour, turbidity, and possible   Water content (mg/kg at transformer operating temperature):
        particle identification. Dark oils might indicate chemical   This is a routine test for all classes of electrical equipment, except
        degradation or contamination of the oil. When there is a lot   class G. The results of this test should always be considered in
        of turbidity, it might indicate a high-water content in the oil.   conjunction with the breakdown strength. If it is found that the
        If the drain valve was not wiped clean by the sampler, the dirt   water content is high, and the breakdown strength is low, further
        particles in the drain valve might be incorporated into the   action needs to be taken. It is recommended that a second sample
        sample. If particles are identified as carbon, it might indicate a   from the same unit be tested to confirm the results. In the case
        possible electrical fault in the unit. The DGA analysis of the oil   of switching equipment, where there is no paper present, the
        will confirm if this is the case. Clear oils without contamination   breakdown voltage is the determining factor.
        will indicate a good condition, and no action is recommended.   It should be noted that the limits indicated by IEC 60422 Edition
        When oils are dark or turbid, further analysis will confirm any   4 apply to transformers with operating temperatures between 40
        problems. The oil analysis results will also determine the degree   and 70°C. If it is found that the unit’s operating temperature is
        and type of action.                                    outside this temperature range, it is best to refer to Annex A of the
                                                               standard. When the value obtained through analyses is good, the
        Breakdown voltage: This is a routine inspection. Breakdown   normal sampling interval can be maintained, requiring no further
        voltage will indicate the water content or the presence of   action.
        foreign particles, or both, in the oil being analysed. As the oil in   •  When the value returns a fair result, more frequent sampling is
        transformers acts as an insulation medium to avoid flashover in   recommended.
        the unit, the breakdown voltage must be high.
        •  If the values are “good”, it is recommended to continue with   It is also helpful to consider other parameters such as the
          the current sample interval action plan.             breakdown voltage, particle content and DDF/resistivity, and acidity
        •  If the values are “fair”, more frequent sampling is   to decide on the action to be implemented.
          recommended in collaboration with other parameter results   •  A poor result will require immediate action from the asset
          such as the water content, DDF (dielectric dissipation factor),   manager.
          and acidity.
        •  If values are “poor” it is recommended to recondition the   This might include taking another sample to confirm the results
          oil. If alternative tests indicate severe ageing, the oil can be   from the first analysis. If it is confirmed that the water content
          replaced with new or reclaimed oil. Another option would be   is high, the oil can be filtered; this process should remove a
          to perform on-site oil reclamation using a reclamation plant.   large portion of the moisture from the oil if applied correctly.
          Reclamation of oil has the advantage that the colour of the   Follow-up samples need to be taken to ensure that the moisture
          oil is restored, and the polar components are removed from   content is still within the required limits. The reason is that the
          the oil. This process removes acid and water as well as some   most significant portion of the water is absorbed in the paper
          other compounds.                                     of the transformer. This moisture will move from the paper into
                                                               the oil under conditions that favour this movement. It might be
        Another advantage is that the oil can be re-used, and in most   found later that the oil in the water has increased again without
        situations, this can be done without switching off the unit,   any apparent reason, but the source would be the paper in the
        which contributes to cost-saving. If in doubt, switch off the   transformer.
        unit during this treatment process. If the values are poor,   A visual inspection is also recommended to determine if any
        it is advisable to act as soon as possible and not delay the   water might move into the transformer or electrical equipment
        maintenance process.                                   through leaks. This problem might be more severe if the
           Excess water in the transformer system decreases the   transformer or electrical equipment is outside and not in a covered
        projected transformer lifetime significantly; extremely high-  area.




















                                                    energize | June 2022 | 56