Page 8 - Energize September 2022
P. 8

COVER STORY


                                                               Stage 1: PF analysis
                                                               An increase in power factor, measured at power frequency, was
                                                               observed on two of the three bushings (X 1 and X 3), as shown in
                                                               Table 2.
                                                                  According to IEEE C57.152, the line frequency PF values for
                                                               X 1 and X 3 at 20°C exceed acceptable limits, while according to
                                                               CIGRE TB 445, the PF values of bushings X 1 and X 2 are within limits
                                                               with only bushing X 3 outside acceptable limits. Based on these
                                                               results alone, we may say that bushings X 1 and X 3 are not in good
                                                               condition, and that bushing X 3 should be further investigated as
                                                               soon as possible.


        Figure 2: Example of a normalised DFR curve alongside the measured curve  Bushing   Nameplate % PF   Measured % PF

           Using the ITC method to accurately normalise results   X1            0.23            0.47
        eliminates the need to wait until the temperature is close to
        20˚C to test a bushing, or to rely on generic correction factors   X2   0.23            0.27
        that may or may not be valid, depending on the insulation
        condition.                                              X3              0.24            1.4
                                                               Table 2: Increase in power factor at power frequency
        Dielectric frequency response (DFR) measurements
        The insulation system of an OIP bushing electrically behaves as   Stage 2: NB DFR analysis
        multiple series capacitors that are formed of conductive foil and   The NB DFR test was carried out on the three bushings at
        oil-impregnated Kraft paper, as previously mentioned. The oil and   frequencies from 1 Hz to 500 Hz. Figure 3 shows an increase in
        paper form a composite dielectric system, and DFR results are a   DF% for bushings X 1 and X 3 at lower frequencies. The thermal
        combination of the responses from the oil and paper components.   response curves are shown in Figure 4 and are different for each
        The responses from both of these components vary with   bushing because of the variations in the dielectric frequency
        frequency, but the way they vary is different and this difference is   response between the bushings. Table 3 shows the temperature
        exploited in DFR testing.                              corrected  PF% values.
           When NB DFR testing does not provide a definitive indication   For a bushing in good condition, its C 1 PF test result is only
        of the condition of a bushing, DFR testing, which is carried   slightly temperature dependent. As its insulation ages and
        out over a wider range of frequencies, can be used for a more
        in-depth analysis. Analysis of DFR curves can yield important
        information, such as the moisture content of the paper and the   Bushing   % PF at 60 Hz   % PF at 10Hz   % PF at 1 Hz
        conductivity of the oil. In addition, the presence of contamination
                                                                X1          0.454        0.514        1.32
        or other physical issues can result in atypical responses with the
        most prominent deviations seen at the lower frequencies.  X2        0.271        0.278        0.66
           DFR measurements are often carried out at 140 V. Because
        the test covers a wide range of frequencies and uses low   X3       1.14         2.76         11.9
        currents, electrical noise can adversely affect the accuracy of the
        measurements, particularly when testing already relatively low   Table 3: Temperature corrected PF values
        capacitance specimens, like bushings. The solution is to test at a
        higher voltage. The use of a voltage amplifier in conjunction with
        a DFR test set greatly improves the signal-to-noise ratio, allowing
        accurate and reliable measurements to be made even in noisy
        environments.

        In the field
        To illustrate and confirm the value of the tests described in this
        article, the same series of tests was performed in the field on
        three OIP HV bushings. The testing was carried out in three
        stages: PF analysis, NB DFR analysis and DFR analysis.  Figure 3: Increase in percentage of DFR at lower frequencies



                                                  energize | September 2022 | 6
   3   4   5   6   7   8   9   10   11   12   13