Page 18 - Issue 3 2023
P. 18

TECHNICAL


               Identifying ageing and installation


                              issues in an HV bushing




        The 69 kV bushings on a 1969-vintage 10 MVA, 69/13,09 kV Dyn1 two-winding transformer were
        subjected to some important electrical tests following the completion of on-load tap changer
        (OLTC) maintenance on this transformer.


                                                 Information from Megger



             his article describes the tests and
             discusses the test results. It shows
        Tthe value of line frequency power
        factor testing when used as the primary
        approach to evaluating HV insulation.

        Overall transformer line
        frequency power factor (LF PF)
        tests
        Losses measured for the low-to-ground
        (CLG) and high-to-ground (CHG)       Table 1: Overall transformer LF PF test results – initial condition
        insulation systems were higher than
        those measured for the interwinding,   temperature corrected LF PF test results for bushings H1 and H2 earned the bushings
        or high- to-low (CHL), insulation system   good (G) ratings while the individual temperature corrected LF PF test result for bushing
        of the transformer. The temperature-  H3 resulted in an ageing (A) assessment.
        corrected (i.e. 20°C equivalent) LF PF   The test results also display an interesting anomaly in the ‘individual temperature
        test results for CLG and CHG insulation   correction’ values. A temperature-correction (TC) factor is used to determine a test
        components were within acceptable    specimen’s 20°C equivalent LF PF value when the specimen is power-factor tested at a
        limits (<0,5%), and even within limits   non-20°C temperature.
        established for new transformers.      An ITC factor is a TC factor that is unique to every test specimen as it is based on the
        However, the CHG LF PF test result   specimen’s specific condition. Note that the ITC factor for bushing H3 (~0.6) is different
        (0,43%) was approximately 1,8 times the   than the ITC factors determined for bushings H1 and H2 (~1,04). The non-uniformity
        CHL LF PF result (0,24 %) (Table 1).  that exists in these ITC factors is a clear indication that the H3 bushing has a different
           Based on recent experiences using   insulation condition than H1 and H2 bushings.
        Narrowband Dielectric Frequency
        Response (NB DFR) testing and successes   Transformer bushing C1 test investigation
        in finding hidden issues not observed   ITC factors are far more accurate than TC factors accessed in a look-up table. To
        by LF PF tests, a NB DFR test was carried   underscore the problem with temperature-correction look-up tables, consider the
        out. A NB DFR test is the measurement   following:
        of % PF or % DF at different frequencies   •  If the end-user had relied on correction tables, the TC factor would have been
        from 1 Hz to 505 Hz.                   determined based upon the average of the ambient and bushing temperatures. This
           In addition, the testing specialist
        performed 10 kV C1 LF PF tests on the
        transformer’s high-side winding bushings
        (Table 2). The H3 bushing produced
        elevated LF PF test results (measured
        and temperature-corrected) that were
        notably greater than results for the
        sister bushings mounted on the same   Table 2: C1 test results for the high-side bushings, including 10 kV LF PF and 250 V NB DFR results,
        transformer. Accordingly, the individual   measured and temperature-corrected via the ITC method


        18 | energize Issue 3 | 2023                                                             SUBSCRIBE FREE
   13   14   15   16   17   18   19   20   21   22   23