TECHNICAL



        Medium voltage circuit breaker



        condition assessment


        Information from Omicron





        Modern industry cannot operate without electricity, and circuit breakers are indispensable in any

        electrical power system. They are the only pieces of equipment which can switch under normal load,
        as well as under fault conditions and must be able to reliably disconnect a faulty section from the
        power network as quickly as possible.






               ircuit breakers must be able  for the opening and the closing operation to be stored. To release the energy stored in
               to meet this requirement even  the springs, two coils are needed to control the springs remotely. The opening spring is
               after they have been in-      charged during the closing operation of the breaker, and the closing spring is charged by
       Cservice for a long time. Their       a motor.
        reliability is essential for the prevention
        of consequential power system failures  Testing of medium voltage circuit breakers
        and the safety of the electrical power  The following is a brief overview of the most important medium voltage circuit breaker
        supply. Typical tests include        measurement methods.
        measurements of operating times and
        the static contact resistance.       Off-service measurement methods
           A more extensive condition        •  Timing: Timing measurements according to the IEC 62271-100 standard are used to
        assessment is possible when further    determine operation time and belong to the most common tests. The timing test uses a
        measurements are performed, such as    resistance or voltage threshold to determine the state of the main contacts.
        motion/contact travel measurements,  •  Static contact resistance: This test verifies whether the resistance of the main contacts
        or the measurement of the motor        allows the current to flow with minimal losses.
        current signature.                   •  Dynamic contact resistance: This records the contact resistance during the operation of
           For circuit breakers that are equipped  the breaker and delivers information about wear-related problems with main and arcing
        with an under-voltage release or an over-
        current release, testing these features
        further increases the available information
        that can be used during the condition
        assessment of the circuit breaker.

        Medium voltage circuit breakers
        While old medium voltage (MV) circuit
        breakers often used oil as an interrupting
        medium, more modern types almost
        exclusively use vacuum. Essential
        elements of a breaker include the
        interrupter unit, the mechanical linkage,
        and the operating mechanism with an
        energy storage system. The energy
        needed to operate a circuit breaker is
        high, and it must be made available within
        a few milliseconds, i.e., almost
        instantaneously.
           Springs are used in most cases
        because they are simple and reliable.
        Two separate springs allow the energy  Figure 1: Under-voltage release test signal