Page 64 - Energize November 2021
P. 64

TECHNICAL


        Input stage developments
        The purpose of the input stage is to
        convert incoming AC from the grid to
        DC for the DC bridge. This involves AC/
        DC conversion through rectification. The
        simplest input stage consists of a passive
        bridge rectifier circuit, using high power
        diodes feeding into a DC bus. The diode   Figure 4: A six-pulse (three-phase bridge) rectifier (WEG)
        bridge will only conduct when the input
        voltage rises above the DC bus voltage,
        resulting in zero current flow for part of
        the input cycle.
           The starting point will be the basic
        three-phase rectifier bridge configuration,
        which leads to what is known as the six-
        pulse system. Figure 4 shows the rectified
        voltage and current waveforms. This
        results in a distorted current waveform
        that has a nonlinear periodic form (more
        commonly known as a pulsed waveform).
           The shape of the current waveform
        will depend on the point at which the
        diode conducts, which varies as the load
        varies, and the harmonic content will
        vary with load. The waveform shows a   Figure 5: Broadband passive filter (Schneider)
        strong ripple. This wave form is rich in
        harmonics, mainly the 5th, 7th, 11th   bulky, show a considerably large voltage drop across the filter chokes at nominal load, and
        and 13th harmonic components, and    often result in increased DC-link voltage in no-load or light load conditions.
        the typical total harmonic distortion of   When the drive is off, the capacitor can cause power factor and voltage rise problems,
        input currents (THDi) is slightly below   and in the event of capacitor failure, standard units offer no indication of this failure. In
        48%. These rectifier systems do not fulfil   addition, they show a low power factor at partial load. The tuned filters could resonate with
        the requirements outlined in industry   the grid supply frequency, or with existing harmonics on the grid, and have to be damped,
        standards, where a total THDi of only 5%   which reduces their efficiency. These filters have a relatively low cost compared to multi-
        is demanded.                         pulse converters. Overall, they are not considered the best choice for implementing a low
                                             harmonic MV input stage.
        Harmonic mitigation
        Methods adopted to reduce harmonics   Active harmonic correction filters
        include:                             Active harmonic correction units are high-performance inverters which measure system
        •  Passive filters                   harmonics through current transformers and inject harmonics of equal amplitude and
        •  Active filters                    opposite phase into the system. These systems are very expensive and are rarely applied
        •  Multipulse rectifier systems      for low-diversity, high-power applications. They can be well-suited to systems where low
        •  Active front end systems          power loads are numerous and diverse, as a single active filter can be applied to mitigate
                                             the harmonic distortion effects of many drives.
        Passive filters                        Active harmonic correction filters also can make an excellent retrofit for existing
        Several possibilities are available to   systems because they are a shunt-connected device. When lightly loaded, most devices can
        comply with stringent input current   correct power factor using the capacitance built into them. Drawbacks to this technology
        harmonic requirements. One method    include the high cost per unit of power and lower energy efficiency.
        used to reduce low-frequency harmonics
        is the application of passive filters   Multi pulse systems
        tuned to the low harmonics, mainly to   Multipulse solutions, such as 12-pulse, 18-pulse, or 24-pulse rectifier systems, use a
        the 5th/7th and 11th/13th harmonic   transformer with two or more phase-shifted windings and diode bridges. Due to the
        components. A primary inductor with   phase shift in the different windings, some low-frequency harmonics are compensated on
        relatively high impedance blocks higher   the primary side of the transformer. These systems show a high efficiency as well as the
        order harmonics. Due to their low tuned   advantage of already including the transformer to the MV side in the drive. However, the
        frequency, these filters are very heavy and   high complexity and cost of the transformer can outweigh these advantages. 4



                                              energize | November/December 2021 | 62
   59   60   61   62   63   64   65   66   67   68   69