           In Figure 2, the column Δ%PF refers
        to the difference between nameplate
        and measured percentage PF values
        corrected to 20°C. As done with the
        overall PF testing performed on the
        transformer, 1 Hz PF test results were
        collected for the bushings as well
        (Figure 3).





                                             Figure 4: HV bushing removed from the transformer – surface contamination on its lower insulator

                                               Not surprisingly, the 1 Hz PF test results confirmed the need to investigate all HV
                                             bushings. The asset owner ultimately decided to replace the HV bushings. The transformer
                                             oil was drained and the HV bushings were removed from the unit. Figure 4 shows a layer of
                                             contamination on the bottom section of the bushings.
        Figure 2: HV bushings LF PF values (DF or   Based on these findings, the owner decided to filter the oil to ensure the removal of
        tangent delta) – measured and corrected by ITC
                                             all in-tank particulates. New bushings were installed and tested. Excellent LF (Figure 5)
                                             and 1 Hz PF (Figure 6) values were obtained.

                                             Test conditions were:
                                             •  Ambient temperature (T A) = 12°C
                                             •  Transformer top oil temperature (T OT) = 37°C
                                             •  Bushing temperature (T avg = (T A + T OT)/2) = 24,5°C


                                             With the HV bushings replaced, the oil filtered, and under similar test conditions, the overall
                                             LF PF test was carried out and results show clear improvement (Figure 7).
                                               As with the LF PF values, 1 Hz PF test results did improve as shown in Figure 8, but
        Figure 3: HV bushings 1 Hz PF (DF or tangent   assessment indicates that the unit requires further investigation. Why would the 1 Hz PF
        delta) – measured and corrected by ITC  values still be high after HV bushings replacement and oil filtering?
                                               To answer this question, the asset owner requested a definitive analysis of the
                                             transformer’s insulation system, using the IDAX300 test instrument, to obtain a complete
                                             dielectric frequency response (DFR).
                                               Full-spectrum DFR shows that the interwinding solid insulation contains a typical
                                             percentage moisture (1,7 %) for a service-aged transformer but the liquid insulation reports
                                             high conductivity (11,8 pS/m).
                                               Further internal inspection of the unit revealed that the tank walls and paper insulation
                                             retained contamination in areas making it difficult to remove. It was recommended to flush the



        Figure 5: New HV bushings LF PF (DF or tangent
        delta)
















        Figure 6: New HV bushings 1 Hz PF (DF or   Figure 7: Overall LF PF (DF or tangent delta)   Figure 8: 1 Hz PF results after HV bushings
        tangent delta)                       results after HV bushings replacement.  replacement