Page 52 - Energize January 2022
P. 52

TECHNICAL



                                                                                    A full-spectrum analysis (DFR) with
                                                                                  a Megger IDAX300 (Figure 11) is the
                                                                                  definitive method to determine the
                                                                                  condition of solid and liquid insulations.
                                                                                    For a service-aged transformer, the
                                                                                  recommended maximum limit of moisture
                                                                                  is <2% and the recommended limit for
                                                                                  liquid insulation conductivity is <37 pS/m.
                                                                                    Surface contamination of the solid
                                                                                  insulation and tank walls must be analysed
                                                                                  in the laboratory. Sediments and particles
                                                                                  must be properly identified to better
                                                                                  understand the source of such material.
                                                                                    Be proactive, not reactive, and make
        Figure 9: Dielectric Response after oil processing                        sure that you are equipped with the right
                                                                                  tools to make the right decisions.
        core coil assembly several times to remove   regions. T 1 and T 2 are part of the six basic
        contamination. Samples were taken and   types of faults or stresses in transformers   Benefits
        sent to the laboratory for analysis.  identifiable with the Duval Triangle 1. T 1   The main concern is always safety. Proper
           It is important to mention that   corresponds to thermal faults < 300°C, and   screening of the electrical assets that
        historical DGA data (Figure 10) did not   T 2 corresponds to thermal faults between   personnel work around is paramount in
        alarm the operator. In the Duval Triangle   300 and 700°C.                reducing risk of unexpected failure(s)
        1, values fluctuated within T 1 and T 2                                   and collateral damage. In this case,
                                             Takeaways                            a thorough screening identified a
                                             Line frequency PF (DF or tangent delta)   transformer that may have suddenly
                                             measurements by themselves may or    failed due to dielectric breakdown,
                                             may not reflect the true condition of the   overheating or thermal runaway.
                                             insulation system inside a transformer.  While lab results must confirm, the likely
                                               It is fundamental practice to record   source of contamination is the compromised
                                             a benchmark signature of the dielectric   pump. Even flushing the transformer several
                                             condition of a power transformer before   times may not guarantee a residual-free
                                             any maintenance work is carried out.  environment for the liquid and paper
                                               Look beyond the information provided   insulation. The significantly better screening
                                             by LF PF. 1 Hz (as demonstrated in this   tool of 1 Hz PF and a full DFR test will
                                             case study) and 500 Hz complement LF PF.   provide some perspective about the success
        Figure 10: DGA identified fault condition from
        2009 to 2021 for the 1978 transformer of this   Practical references are now available to   of a flushing remedy. Should conductive
        case study                           assess 1 Hz and 500 Hz PF test results.  contaminants remain, however, the
                                                                                  transformer design is invalid, and the asset
                                                                                  owner assumes elevated risk of failure. In
                                                                                  this event, the transformer may need to be
                                                                                  replaced as soon as possible. Alternatively,
                                                                                  this transformer may be derated with some
                                                                                  manufacturer guidance, and, for example, be
                                                                                  used or relocated to an area where load will
                                                                                  not exceed 50% of rated capacity.

                                                                                  Reference
                                                                                  1. Diego Robalino: Transformers Magazine,
                                                                                   https://transformers-magazine.com/
                                                                                   magazine/2139-individual-temperature-
                                                                                   compensation-power-transformer/

                                                                                  Contact Kenneth Petroff, Megger,
                                                                                  Kenneth.petrof@megger.com,
        Figure 11: Megger IDAX300 DFR insulation diagnostic instrument            www.megger.com



                                                   energize | January 2022 | 50
   47   48   49   50   51   52   53   54   55   56   57