Page 50 - Energize January 2022
P. 50

TECHNICAL


        Misleading line frequency insulation


        results on a contaminated transformer



        Information from Megger





             1978 vintage, 20 MVA, 69/13,09 kV,   Traditional analytic guidelines suggest that these temperature-corrected LF PF test
             Dyn1 transformer, operating for a   results are indicative of an insulation in acceptable condition. Modern learning, however,
        A major North American utility, was   cautions that LF PF test results alone no longer provide a sufficient screen.
        taken out of service to repair a pump in the   Accordingly, as part of the power factor test, 1 Hz PF was also measured and corrected
        cooling system. The technical maintenance   to 20°C equivalent values (Figure 1). The 1 Hz PF test results are much greater than
        team completed the required repairs and   those recommended for service-aged transformers, as flagged by the software with an
        conducted a complete protocol of routine   Investigation (I) rating.
        commissioning tests, including a 10 kV line
        frequency (LF) power factor (PF) test.  The C1 insulation systems of the HV bushings were also tested.
                                             The conditions during testing were:
        The investigation                    •  Ambient temperature (T A) = 15°C
        The insulation condition of the      •  Transformer top oil temperature (T OT) = 30°C
        transformer was evaluated in the     •  Bushing temperature (T avg = (T A + T OT)/2) = 22,5°C
        field after pump repairs. The overall   •  All HV bushings’ line frequency power factor (LF PF) test results were higher than desired,
        capacitance and line frequency power   with power factor values double or nearly triple the nameplate values.
        factor (LF PF) test at 10 kV was performed
        using Megger’s DELTA4000 power factor   These test results warranted investigation.
        (dissipation factor) test set.
           The LF PF test results obtained at   An additional diagnostic clue that something is amiss with these bushings is their
        30°C top oil temperature (T OT), and   temperature sensitivity. The typical variation of LF PF between 20 and 22,5°C should be close
        then properly corrected to their 20°C   to zero. For example, bushing H2 measures 0,72% PF at 22,5°C. At a mere 2,5°C difference,
        equivalent values using the individual   the expectation is that bushing H2 would also measure approximately 0,72% PF at 20°C.
        temperature correction (ITC method)    However, ITC reveals very different dielectric behaviour (Figure 2) of these bushings, i.e., an
                                   1
        are presented in Figure 1.           extreme temperature sensitivity.


































        Figure 1: Transformer overall LF and 1 Hz PF test (PowerDB screen shot)



                                                   energize | January 2022 | 48
   45   46   47   48   49   50   51   52   53   54   55