Page 60 - Energize May 2022
P. 60

TECHNICAL


        What is melting here? Time for an


        SFRA test



        This case study was generously supplied by the Hitachi Energy Service group in Sweden

                                                 INFORMATION FROM MEGGER



              22 MVA, 10,5 kV/276 V (voltage   ratio, winding resistance, insulation resistance, and sweep frequency response analysis (SFRA).
              regulation from 336 to 216 V), Diii   Additionally, oil samples were taken for laboratory analysis of dissolved gases in oil (DGA).
        A furnace transformer, operating       Transformer turns ratio tests were performed with LV excitation from the HV side. A
        in heavy use for many years at a steel   winding connection Dd0 was used for measurement. Transformer turns ratio tests were
        melting plant in Europe was subjected to   performed on all taps and acceptable values were obtained for two phases. The test
        a complete series of tests after a sudden   instrument was unable to perform ratio measurements on phase C. This may have been
        failure during operation. The service   attributed to a state where the impedance was so low that the test instrument was unable to
        contractor evaluated the electrical and   build up the excitation voltage configured for the test.
        dielectric condition of this transformer.   The transformer turns ratio results are presented in Table 1. Winding resistance tests
        During service, this type of transformer   were then performed on the transformer. Table 2 presents the HV-side winding resistance
        has its secondary winding connected   measurements performed in the factory (RFAT average) and the field.
        externally in a Delta configuration through
        a high current bridge. To clarify the vector
        designation, a simple diagram showing its
        terminals is presented in Figure 1.


        Investigation
        An outage of a furnace transformer is
        devastating for the industrial operator.
        Loss of power results in loss of production.
        Fortunately, in this case, a spare
        transformer was available on-site. This
        afforded an opportunity for the service
        contractor to perform several tests on the
        faulted unit, including transformer turns




                                             Table 1: Turns ratio results on all tap positions
























        Figure 1: Furnace transformer with winding
        configuration Diii                   Table 2: Factory and field winding resistance measurements (HV winding)



                                                    energize | May 2022 | 58
   55   56   57   58   59   60   61   62   63   64   65