Page 61 - Energize May 2022
P. 61

TECHNICAL



           Winding resistance results are
        usually interpreted based on comparing
        measurements made separately on each
        phase of a wye-connected winding or
        between pairs of terminals on a delta-
        connected winding. A comparison may
        also be made with original data measured
        in the factory.
           A measurement is deemed
        acceptable, and no further investigation
        is needed, if the individual phase
        readings are within 2% of the other   Figure 2: Winding resistance measurement corrected to FAT for comparison
        phase readings for three-phase
        transformers or within 2% of the
        reported factory values. When
        readings are outside the 2% range,
        it is recommended to investigate
        further, or to consult the transformer
        manufacturer to determine the
        acceptability of the results. However,
        for very low resistance values, it is
        not uncommon for measurements to
        be outside of the 2% limit even in a
        perfectly normal transformer. In such   Figure 3: Percentage variation with respect to FAT measurements
        cases, the measurement tolerances of
        test equipment may be insufficient to   observed in this transformer were better visualised in the resistance measurement plot
        resolve the acceptable 2% limit between   (Figure 2) and the graphed error, given in percentages (Figure 3).
        measurements. 1                        The plot in Figure 2 shows an elevated value of winding resistance test results as
           According to IEEE C57.152 , values   compared to FAT values but of most significant note is the variation of phase C.
                              2
        above 5%, as compared against factory   Figure 2 shows that phases A and B behaved similarly with increasing variation with
        records, should be investigated.     respect to FAT measurements as the tap position changed. Taps 9, 10, 11, 12 and 13 would
           In this case, the factory values   unequivocally be considered for investigation as the difference is >5%.
        were obtained at 24,7°C and field      Phase C behaved quite differently, exceeding acceptable variation on all tap positions.
        measurements were made at 28°C.      Phases A and B were affected by the fault in phase C, as the windings in operation were
        Correction to factory values is      Delta connected.
        performed as suggested in  following   Winding resistance test results on the LV side are presented in Table 3. The table
                           2
        equation (1).                        provides test results for one section of the LV winding. The other sections of the LV winding
                                             yielded similar results.
        R s = R m ((T s + T k) / (T m + T k ))   (1)


        Where:
        R s = Resistance at reference temperature  Ts
        R m = Resistance at measured temperature  Tm
        T k – 234,5°C (copper) and 225°C
        (aluminium)
                                             Table 3: Factory and field winding resistance measurement (LV winding)
        The results revealed a mess. The phase
        C winding resistance was a concern on   Next, the test crew attempted to perform an insulation resistance test at 500 VDC; these
        tap position 1 and, as the tap position   results are presented in Table 4.
        changed and additional portions of the
        tap (or regulating) winding were added,
        the results substantially deteriorated
        further. Phase A and phase B test
        results were unacceptable at higher tap
        positions too. The significant differences   Table 4: Insulation results obtained at 28°C



                                                    energize | May 2022 | 59
   56   57   58   59   60   61   62   63   64   65   66