Page 62 - Energize May 2022
P. 62

TECHNICAL



           An oil sample was taken from the transformer and sent to a lab for a DGA test. Results   All evidence clearly pointed to
        are shown in Table 5.                                                     a fault inside the transformer. The
                                                                                  remaining question was, where? To
                                                                                  localise the fault in the overall active
                                                                                  part of the transformer, SFRA testing
                                                                                  was carried out using Megger’s FRAX
                                                                                  101.
        Table 5: Gas concentration from a transformer oil sample                    SFRA open circuit test results
                                                                                  (Figures 5 and 6) indicate a short circuit
        The “latest before failure” DGA test results are not representative of a gassing issue,   in phase C (blue traces). The fault had
        especially for a furnace transformer. Numbers fall under condition 1 as specified by existing   also affected the other two phases,
        standards. This is a case where only an on-line gas monitor or a ‘lucky’ oil sample may have   resulting in a completely asymmetrical
        detected the incoming arcing fault before failure.                        response.
           The post failure DGA analysis indicates a D2 position in Duval’s Triangle 1, as well   SFRA HV short circuit test results
        as in Pentagon 1. D2 is an indication of “high energy discharge including arcing, with   confirm that phase C was affected
        expected metallic fusion and presence of carbon particles in the oil.” These results are   in this transformer but also that this
        presented in Figure 4.                                                    damaged phase affected the response
                                                                                  of phases A and B.
                                                                                    It was obvious that the transformer
                                                                                  required major work before returning it
                                                                                  to service. To evaluate the extent of the
                                                                                  damage identified by this series of tests,
                                                                                  the asset owner ordered an internal
                                                                                  inspection.
                                                                                    During the inspection, the fault was
                                                                                  observed on the phase C regulating
                                                                                  winding as shown in Figure 8. The A and
                                                                                  B phase windings, as well as the core,
                                                                                  were undamaged.
                                                                                    The asset owner decided to have
        Figure 4: Duval’s fault analysis of the oil sample taken after the failure of the transformer
                                                                                  the unit repaired. The unit was taken to
                                                                                  its manufacturer’s repair shop for full
                                                                                  restoration and returned to service.
                                                                                    The root cause of failure is not 100%
                                                                                  clear. This furnace transformer was in
                                                                                  heavy use for many years, with the full
                                                                                  power frequently switched on and off.
                                                                                  The condition of the transformer was
                                                                                  never investigated thoroughly before
                                                                                  the fault occurred.

                                                                                  Conclusions
                                                                                  During the service life of a power or
        Figure 5: High voltage open circuit – Tap position 1
                                                                                  distribution transformer, it is almost
                                                                                  impossible to prevent transient
                                                                                  events and through-faults which can
                                                                                  severely damage the active part of the
                                                                                  transformer. After many years in service,
                                                                                  especially for furnace transformers, it
                                                                                  is beneficial to thoroughly evaluate the
                                                                                  operational condition. For service-aged
                                                                                  transformers, the operational profile
                                                                                  may need to be modified so that the
                                                                                  transformer continues to withstand
        Figure 6: High voltage open circuit – Tap position 13                     operational stresses.



                                                    energize | May 2022 | 60
   57   58   59   60   61   62   63   64   65   66