Page 44 - Energize September 2021 HR
P. 44

TECHNICAL

        Obtaining power quality grid-code



        compliance for a wind farm





        by Kyle Lass, RWW Engineering; Dirk van der Bank, ADAee; and Aki Tiira, Merus Power Dynamics Oy



        Grid-code compliance was recently achieved for a wind farm in the Eastern Cape, after the installation of
        active harmonic filtering (AHF) to mitigate plant generated harmonic emissions. This is one of the largest
        installations of its kind in the world. Some of the requirements and technical challenges overcome are
        highlighted in this article.






            he 132 MW wind farm, comprising of sixty 2,3 MW wind   level with the transformer impedance used as a buffer between plant
            turbines, went into commercial operation after being granted   generated and grid related flicker content.
        Ttemporary exemption on the harmonic current emissions    The wind turbine generators provide power at a nominal 690 V
        from the plant into the network. After fine tuning the wind turbine   level. This voltage is transformed from 690 V to the distribution
        inverters, it was still required to mitigate high levels of current   33 kV via transformers local to each wind turbine. The Merus A2
        emissions at the second and fifth harmonic orders. This was   active harmonic filter generates the compensation currents at 400V
        measured at the point of coupling to the 132 kV network.   and is connected to the 33 kV network via a 5000 kVA, 400 V/33 kV
           A 2700 A (at 400 V) Merus A2 active harmonic filter was supplied   three-winding transformer.
        and installed by RWW Engineering to fulfill the harmonic cancellation   Effectively this translates the seemingly modest level of
        requirements and achieve compliance to the South African Grid   harmonic current mitigation requirement at grid level to very high
        Code for renewable power plants (RPP). Grid-code compliance   levels of injected harmonic current at the 400 V level. For example,
        recordings and confirmation studies for the project were performed   the need for a mere 5,5 A of harmonic current compensation at
        by ADAee.                                              grid 132 kV level equates to more than 1815 A of harmonic current
                                                               injection required at 400 V.
        Regulations and standards
        Renewable power plants wishing to connect to the South African   Control systems to interface at various bus voltage levels
        national grid must comply with regulatory specifications as set out   The wind farm in question previously achieved compliance to all
        by the national energy regulator. The relevant power quality (PQ)   PQ parameters according to agreed limits with the national energy
        parameters are defined in the grid code. For this plant, the category   regulator, other than current harmonic emissions at the second and
        C (20 MVA and larger) provisions are applicable. The latest update   fifth harmonic orders. These emissions were in the region of 5,5 A
        is Revision 3, dated August 2019. In addition, the specific limits   at 132 kV. Various proven methodologies were undertaken prior to
        for each of the defined parameters are also contractually agreed   implementing the active filter to ascertain whether these harmonic
        and assigned to each individual RPP. Several further guidelines   currents were indeed coming from the RPP or whether the RPP was
        and standards support the above specification and ensure a   absorbing these harmonics from the grid network. After exhaustive
        standardised approach in collecting and analysing data from   testing, simulation and online plant controller modifications, it was
        operations, including standards and guidelines as per various NRS,   proven that the second and fifth harmonic currents were mostly
        IEC and Cigré papers.                                  being generated within the RPP and exported to the grid network.

        Case study of wind farm challenges and solutions
        Control systems to interface at various bus voltage levels
        The point of connection (POC) for the WF (the point at which full
        PQ compliance must be demonstrated) is on the national grid at
        a 132 kV bus voltage level (Figure 1). The permanently installed
        highly accurate metering PTs and CTs are used to record voltage
        and current trends. These recordings effectively determine harmonic
        voltages, harmonic currents, flicker, resonance sensitivity and
        voltage unbalance conformance to the contractual limits.
           The plant itself collects power at the 33 kV level from the wind
        turbines. Therefore, there is a need for a step-up transformer
        between the internal wind farm level at 33 kV and the grid at 132 kV.
        Flicker compliance is determined from this internal 33 kV voltage   Figure 1: High level SLD wind farm with Merus A2 active harmonic filters



                                                  energize | September 2021 | 42
   39   40   41   42   43   44   45   46   47   48   49