Page 45 - Energize September 2021 HR
P. 45

TECHNICAL



        These findings were verified by the national energy regulator which
        oversees the compliance of all the RPPs. Therefore, the RPP was
        liable to reduce these harmonic levels to within acceptable limits,
        within a certain time frame.

        Mitigation solution alternatives
        Mitigating harmonic content on a supply line can be achieved
        via various methods. For example, a passive harmonic filter
        can be designed which involves capacitance and inductance
        elements, tuned towards the harmonic current frequency to be
        trapped and dissipated, rather than to be let through to the grid.
        Consideration should be given to unwanted resonance conditions
        at nearby harmonic orders. Passive harmonic filtration is the
        industry standard throughout the world for harmonic generators,
        such as mining and commercial operations, which have very well
        documented and steady state harmonic emissions. It is generally
        easy and relatively cheap to implement passive harmonic filters, as
        these filters are made from discrete components (capacitors and
        inductors). These filters also have some fundamental frequency
        losses. These operating losses reduce the kWh output of the wind
        farm accordingly.
           Over the lifetime of the wind farm, these losses would
        accumulate into a large monetary value, which would be
        much greater than the initial cost and operating losses of
        an active type filtering system. In this case, these passive
        filters were not an option, as the harmonics in question were
        too close to the fundamental frequency (second) and were
        constantly changing based on the output of the RPP (based
        on wind speed).
           The operating losses calculated were high and the RPP also
        has very strict resonance compliance conditions which limited the
        implementation of passive harmonic filtration equipment. Passive
        harmonic filters also take up a significant amount of space due to
        their required safety clearances. Many RPP’s do not have the real
        estate available for a passive filtering solution with multiple steps
        catering for each harmonic order.
           The second option for harmonic mitigation would be via
        active harmonic filters, whereby offending harmonic currents
        are cancelled or reduced via injection of inverse harmonic
        currents in real time. This is an attractive solution if the offending
        harmonic currents are at multiple harmonic orders, if the
        orders may vary over time, or include very low harmonic orders
        (second) to be mitigated.                              Figure 2: New protection and control panel implemented
           Active harmonic filters further reduce the probability of further
        resonance conditions (as per passive filters) and can also be   An active harmonic filtering system is modular, as can be seen
        configured for a closed loop control. The closed loop control   from Figure 1. This means that if there was a fault in one active filter
        solution is based on the real-time measurement of harmonic   module, the system loses only that portion of its compensation
        content by the AHF, followed by the real time generation and   capacity since the active filter modules used in this case each have
        injection of cancelling harmonic current.              an independent controller. The active harmonic filter compensation
           An additional advantage of an active harmonic filtering solution   currents and harmonic orders can also be changed in real time by
        over a passive one is modularity. Passive filters are typically   the client.
        designed so that there is one filter per harmonic frequency. This
        means that if there is a failure in any of the filter’s components,   Transformer design parameters
        that harmonic frequency is left unmitigated until the filter is   With the active harmonic filter delivering harmonic cancellation at
        repaired. Should the harmonic emissions change over time due   400 V, a step-up transformer is required for interfacing towards
        to system impedance changes by the grid operator, passive   higher plant 33 kV voltage levels. Due to harmonic content, such a
        filters would need to be physically reconfigured and some of the   transformer is bound to be suitably rated (i.e., suitable K-factor) and
        inductance or capacitance values would need to be replaced.   have a means for dealing with heat generation due to skin-effect
        Due to the long lead time of the passive filtering components, this   harmonic current flow (at the internal transformer conductors). The
        could take up to six months.                           losses from this transformer should also be very low to enable the



                                                  energize | September 2021 | 43
   40   41   42   43   44   45   46   47   48   49   50