Page 71 - Energize October 2022
P. 71

TECHNICAL



        •  12% decrease in total weight                        In the event of failure, the force applied to the structure
        •  11% decrease in case weight                         may approximate 360 PSI due to the steep wave front and
        •  10% decrease in oil weight                          high velocity, representing a loading sufficient to distort the
                                                               container or shear the holding bolts and possibly cause a
        •  13% decrease in core & coil weight                  transformer oil fire.
        •  7 to 33% decrease in electrical clearances
        •  9% decrease in no-load losses                       Case example: rectifier transformer
        •  3.5% decrease in load losses                        The DGA on this transformer showed abnormal gas production
        •  25% increase in number of pumps                     of hydrogen, methane, ethylene and ethane about 20 months
        Table 1: Transformer comparisons between the 1970s and 1980s  after energising. The fault condition was diagnosed as a thermal
                                                               fault of medium temperature in the range 300°C and 700°C. The
        What causes a power transformer to fail?               recommendation at 30/09/1996 was to remove the unit from
        It is generally believed that failure occurs when a transformer   service for inspection.
        component or structure is no longer able to withstand the   See Table 2 giving the name plate data and Figure 4 shows
        stresses imposed on it during operation.               the DGA trend with Figure 5 showing the DGA signature.
           It is also important to distinguish the fault and the failure.
        A fault is mainly attributed to permanent and irreversible   Make:      TRAFO-UNION
        change in transformer’s condition. The risk of a failure   Year Manufactured: 1995
        occurrence depends not only on the stage of the fault   Primary Voltage:   132 kV
        developing but also the transformer functional component   VA Rating:   93.5 MVA
        involved. The failure could be repairable on site, depending on   Vector Group:   111,D11+1
        the type of fault as well as the severity of the failure.  Secondary Voltage:  1060V

                                                               Tap Changer:     On Load
        Power transformer failures are commonly associated with   Oil Volume Litres:   33908
        localised stress concentrations (faults), which can occur for
        several reasons, including:                            Conservator:     Yes
        •  Design and manufacture weakness, e.g., poor design   Table 2: Name plate data
           of conductor sizing and transpositions, poor joints,
           poor stress shield and shunts, poor design of clamping,
           inadequate local cooling, high leakage flux, poor
           workmanship, etc.
        •  Weakness in transformer design, construction and
           materials could be covered by low loading. However,
           increasing loading and extended periods of in-service
           usage will uncover these weaknesses



                                                               Figure 4: DGA trend up to July 2001











                                                               Figure 5: DGA Signature up to July 2001

                                                               Condition monitoring and failure event:
                                                               Bay 22 rectifier

                                                               The manufacturer’s contention was that, although this was
                                                               not a normal gassing pattern, it was not serious enough to
                                                               warrant removing the unit from service. The manufacturer’s
                                                               in-house expert advice was to monitor the gassing pattern until
                                                               exponential increase was seen.
        Figure 3: Catastrophic transformer failure                The exponential rise can be seen from 1996 to 1997.



                                                   energize | October 2022 | 71
   66   67   68   69   70   71   72   73   74   75   76