        Conclusions                                            of warranty failure. As one example, National Grid (UK) has
        Fault and failure investigations on power transformer components   reported, “A number of faults have been detected, although in
        have an important role in improving reliability and managing the   each case the transformer had satisfactorily passed the routine
        risk of transformer failure. The identification of the primary cause   tests”
        of failure and the subsequent analysis enables recommendations   CIGRE report 1984 states that “Dissolved-gas-in oil
        for corrective action to be made that hopefully will prevent   chromatographic is successfully applied to fault detection in the
        similar failures from occurring in the future.         maintenance of large power transformers. Savings which could be
           When design error and/or weaknesses developing over time   achieved are in the region of hundreds of millions of US dollars.
        are uncovered, enhanced monitoring/investigation on sister units   Independent professionals and consultants are only able to
        built by the same manufacturer will help in preventing future   offer their opinions.
        failures and therefore aid in managing the risk of unexpected   Experience and understanding of the diagnostic methods are
        failure.                                               required to make DGA a more exact science and not an art.
           Transformer manufacturers need to balance the cost of
        equipment with reliability.                            Acknowledgements
           The transformer problems at the Hillside smelter fit the Bath   The author thanks and acknowledges the following people for
        Tub Life Cycle Model.                                  their contributions: Sunny Sujan, BHP Billition, Luwdren Moodley,
           The application of DGA was 100% successful in identifying the   Doble Engineering Africa and Piet Goosen, Corporate Consultant
        faults at early life. DGA oil testing is typically a critical first step in   (Power Equipment), Eskom
        any power transformer analysis.
           The DGA technique detects newly formed faults both   This article was presented to EuroTechcon 2011. The unabridged
        accurately and consistently and will locate a fault that cannot be   version can be found at: https://oilwatch.co.za/dissolved-gas-
        detected in any other way. When abnormal gassing patterns have   analysis-at-an-aluminium-smelter/
        been established the unit should be removed from service as
        soon as it is practically possible.                    Contact Oilwatch, Phone +27 87 238-2188,
           Document first year in-warranty problems before out   support@oilwatch.co.za, www.oilwatch.co.za