Page 51 - Energize September 2022
P. 51

TECHNICAL



        Capacitor banks                                        Static VAR generators (SVG)
        Fixed capacitor banks (FCBs) are used where there is a single   The SVG overcomes the problem of a varying PF by continuously
        load, and where there is little variation in PF. The capacitor’s size   monitoring the voltage and current and continuously correcting the
        is chosen to match the PF of the load. FCBs are most commonly   PF. The SVG consists of a combination of capacitors and inductors
        installed at the connection point of the load.         controlled by SCR switches to provide a continuously variable
           Automatic capacitor banks (ACBs) are used where the load and   reactance. A typical example is shown in Figure 5.
        the PF vary over a considerable range. An ACB consists of a bank of   SVGs are available for industrial and commercial use from as low
        capacitors which are switched in and out of circuit according to the   as 2 kVA up to hundreds of kVA.
        instantaneous PF of the combined loads. ACBs are most commonly
        installed at the common point feeding the loads, such as the main
        distribution board.
           PFC-using capacitors may be applied either at a common point
        or individually at each load as shown in Figure 4. The choice will
        depend on the characteristics of the location. With centralised
        PFC there is increased loss in the cables connecting the load to the
        common point. Individual PFC requires a capacitor at each load,
        which can be more expensive than a common PFC.
           Shunt capacitance also acts as a shunt path for harmonics, and
        the reactance will decrease with increasing harmonic numbers.





                                                               Figure 5: Static VAR generator basics (EEP)

                                                               Harmonic correction
                                                               To solve distortion PF problems, there are two options:
                                                               •  Passive PF correction: Improves PF by filtering out harmonics using
                                                                 passive filters. This is typically used in low power applications but
                                                                 is not enough at high power.
                                                               •  Active PF correction: Uses a switching converter to modulate
                                                                 the distorted wave in order to shape it into a sinewave. The
                                                                 only harmonics present in the new signal are at the switching
                                                                 frequency, so they are easily filtered out. This is considered the
        Figure 4: Common vs individual PFC.
                                                                 best PFC method but adds complexity to the design.
        Harmonic resonance
        A serious concern arising from the use of capacitors in an electrical   Passive filters
        power system is the possibility of system resonance. This effect   Passive filters consist of capacitors and inductors tuned to the
        imposes voltages and currents which are higher than would be the   harmonic frequency which needs to be reduced and are used where
        case without resonance. Harmonic resonance in a power system   there is single load, and the harmonic content is stable. The filter
        may be classified as parallel or series resonance, and both types   may be shunt or series form. This is typically used in low power
        are present in a harmonic-rich environment.            applications but is not enough at high power. Passive filters are used
           Parallel resonance causes current multiplication, whereas series   in situations where harmonic distortion is constant, are of fixed
        resonance produces voltage magnification. Substantial damage   design and are thus relatively cheap.
        to capacitor banks would result if the amplitude of the offending   The filter, connected in parallel with the supply, consists of a
        frequency is large enough during resonant conditions. Also, there is   combination of capacitive and inductive components, providing a
        a high probability that other electrical devices on the system would   low impedance path at the tuned frequency. Designed for a specific
        be damaged too.                                        site, passive filters may consist of a filter for a single harmonic
           For this reason, harmonic analysis must be performed   frequency or may consist of a bank of parallel filters covering several
        before installation of a PF improvement capacitor bank, to   frequencies. Figure 6 shows several possible configurations. Filters
        ensure that resonance frequencies do not correspond with   may also be of the damped wideband type used to cover a range of
        prominent harmonics contained in the currents and voltages.   harmonics.
        Filtering efficiency is defined by the impedance ratio of the   There is a move away from passive solutions to active ones
        passive filter impedance and the network impedance, and it   in low and medium-voltage applications. Typical loads, such as
        is difficult to guarantee compliance with standards by using   variable frequency drives, low-energy lighting systems, etc., which
        passive filters                                        incorporate PFC in their design, have a good PF which could lead



                                                  energize | September 2022 | 49
   46   47   48   49   50   51   52   53   54   55   56