Page 53 - Energize September 2021 HR
P. 53

TECHNICAL
















                                                               Figure 6: Simplified equivalent circuit of Figure 5


                                                               negative sequence impedance, making the       ratio non-zero, but in
                                                               the absence of load impedance information it is better to empirically
                                                               evaluate field data before applying the 46BC feature. Prior service
                                                               suggests that a 20%       ratio is sufficient on four-wire networks
                                                               for sensitivity but is not immune to spurious tripping in highly
                                                               unbalanced networks.

                                                               Conclusion
                                                               Broken conductor detection in the distribution grid is a scenario
                                                               which can be suitably detected using the negative phase sequence
                                                               current. When using NPS alone, knowledge of the negative
                                                               sequence impedance of a load is necessary for appropriate
        Figure 5: Equivalent circuit for a broken conductor on a four-wire three-  calculation. A special case exists for three-wire networks, where
        phase network                                          the positive and negative sequence load impedances cancel out
                                                               in a phase discontinuity scenario, allowing utilities with three-
        The key difference between the four-wire and three-wire systems is   wire distribution networks to use        ANSI 46 broken conductor
        the inclusion of the zero sequence in the resultant calculation.   protection in the absence of load impedance data.
        Calculating for i 1:                                      In four-wire systems, the calculation becomes marginally
                                                               more complex, but can be approximated by empirical data, giving
                                                               engineers visibility of the potentially hazardous broken conductor
                                                               scenario.
                                                                  NOJA Power’s OSM Recloser system is equipped with a full
        And assuming that i 2 is negative and acknowledging the topology as   suite of negative phase sequence and broken conductor protection
        a current divider:                                     elements, allowing utilities to capitalize on the benefits of their
                                                               existing asset base and provide sensitivity to this dangerous
                                                               category of fault for a negligible expenditure.   n

                                                               Acknowledgement
                                                               This article was first published in Australasian Power Technologies
                                                               Publications’ 2020 Purchasing Directory and is republished here with
                                                               permission.
        To calculate the minimum broken conductor ratio in a four-wire
        system, we need to know both the zero and negative sequence load   Contact Martin Van Der Linde, NOJA Power,
        impedance. As a rule, there is more zero sequence impedance than   martinv@nojapower.com.au, www.nojapower.com.au


















                           Subscribe to the Energize newsletter:

                    https://www.energize.co.za/home/subscribe/
   48   49   50   51   52   53   54   55   56   57   58